6
LEG ORIENTATION
LEGS
LEGS
GAS PRESSURE REGULATOR INSTALLATION
Gas regulator pressure is preset at 5” Water Column (W.C.) f or natural gas, and 10” W.C.
for propane gas. Minor adjustments may be required based on site specific gas pressure.
Install the regulator as close to the stockpot on the gas supply line as possible. Make
sure that the arrow on the underside of the regulator is oriented in the direction of gas
flow to the stockpot (Fig. 3) and the regulator is positioned with the vent plug and
adjustment screw upright (Fig. 4).
Fig. 3
Fig. 4
The minimum supply pressure (upstream of the regulator) should be 7 -9” W.C. for natural
gas and 11-12” W.C. for propane gas. At no time should the hotplate be connected to
supply pressure greater than ½ psig (3.45 kPa) or 14” W.C.
LEVELING
The Stockpot Range is equipped with legs. Turn the feet at the bottom of the legs in or
out to level the Stockpot Range in the final installed location.
VENTILATION HOOD
T he stock pot should be installed under a suitable ventilation hood. For safe operation and
proper ventilation, keep the space between the stockpot and vent hood free from any
obstructions.