I N T E R N A L C H A N N E L S S E T T I N G S
20
MRBP.424321.001G2 Version 1.0 15/06/2020
In the
«
MAINTENANCE
»
mode it is possible enable or disable selected channel maintenance.
5.2
CHANNEL CONFIGURATION CHANGE
To change channel configuration, it is necessary to enter
«
MENU
» →
«
CHANNELS SETTINGS
»
→ «
INTERNAL CHANNELS
» →
«
CHANNEL 0X
»
→
«
CONFIGURATION
».
CH1: CONFIGURATION
CL
CONNECTION:
PASS.2wires
POSITION:
SN09501668
GAS
TYPE:
C
3
H
8
MEASUREMENT
UNIT:
%LFL
MIN.VALUE:
0.0
MAX.VALUE:
100.0
BLANKING
ZONE:
1.0
THRESHOLD
1
VALUE:
10.0
THRESHOLD
1
HYSTERESIS:
0.0
THRESHOLD
1
RESET:
AUTO
THRESHOLD
2
VALUE:
20.0
THRESHOLD
2
HYSTERESIS:
0.0
THRESHOLD
2
RESET:
AUTO
SAVE
In the
«
CONFIGURATION
»
menu, it is possible to change/set the following parameters:
•
«
CL CONNECTION
»
- current loop connection diagram selection;
•
«
POSITION
»
- detector position name;
•
«
GAS TYPE
»
- target gas type selection;
•
«
MEASUREMENT UNIT
»
- gas concentration measurement unit selection;
•
«
MIN. VALUE
»
- measurement range minimal value set, corresponds to a 4 mA scale mark
on the current loop;
DISABLE
ENABLE