I N T E R N A L C H A N N E L S S E T T I N G S
19
MRBP.424321.001G2 Version 1.0 15/06/2020
5
INTERNAL CHANNELS SETTINGS
To select internal channels settings, it is necessary to enter
«
MENU
»
→ «
CHANNELS SET-
TINGS
»
→ «
INTERNAL CHANNELS
»
.
The list of internal channels is shown in the
«
INTERNAL CHANNLES SETTINGS
»
menu. It is
possible to see brief information about a channel by using the buttons
and
: gas, measure-
ment units, position, channel state. After the channel selection, the channel settings menu is dis-
played.
CH1: TUNING
MAINTENANCE: DISABLED
CONFIGURATION
INPUT CALIBRATION
CHANNEL FACTORY DEFAULTS
The number of the channel is shown in the top left corner of the display (C1-C8).
In the
«
SETTINGS
»
menu it is possible to set/change the following channel settings:
•
«
MAINTENANCE
»
- maintenance mode switching on/off;
•
«
CONFIGURATION
»
- configuration change;
•
«
INPUT CALIBRATION
»
- input calibration parameters change;
•
«
CHANNEL FACTORY DEFAULT
»
- factory default settings.
5.1
CHANNEL MAINTENANCE MODE SWITCHING ON/OFF
At turning
«
MAINTENANCE
»
mode on any contingencies are bypassed, i.e. relay, sound and
LED signalizations don’t go off
. This mode is intended for maintenance service or trouble-shooting of
the detector connected to the channel.
To switch on/off channel maintenance mode it is necessary to enter
«
MENU
»
→ «
CHANNELS
SETTINGS
»
→ «
INTERNAL CHANNELS
» →
«
CHANNEL 0
Х»
→
«
MAINTENANCE
».
CH1: MAINTENANCE