EMI-SSD-1M

 

TUNING GUIDE 

MRBP.424321.001G2

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Saint-Petersburg 

2020 

Содержание EMI-SSD-1M

Страница 1: ...r Address 27 Engels Prospect building 5 litera A Saint Petersburg 194156 Russia Tel 8 800 234 66 90 Website www igm pribor ru E mail support igm pribor ru EMI SSD 1M TUNING GUIDE MRBP 424321 001G2 Sai...

Страница 2: ...5 4 4 ACCESS SETTINGS 16 4 5 CONTINGENCIES ARCHIVE CLEARING 18 4 6 DEFAULT SETTINGS 18 5 INTERNAL CHANNELS SETTINGS 19 5 1 CHANNEL MAINTENANCE MODE TURNING ON OFF 19 5 2 CHANNEL CONFIGURATION CHANGE 2...

Страница 3: ...structure 36 Appendix B Factory default parameters 40 Appendix C Gases configuration factory settings parameters 41 Appendix D Operation modes contingencies signaling and relay actuation description...

Страница 4: ...anuals Only persons with at least the third electrical safety access qualification level having the cer tificate for work on electrical installations up to 1000 V and trained in workplace safety are a...

Страница 5: ...ttings complete list can be found in the guide sections SETTINGS INTERNAL CHANNELS SETTINGS EXTERNAL CHANNELS SETTINGS ARCHIVING MODE SETTINGS At the first start default settings and methane channels...

Страница 6: ...Channel initialization mean time is no longer than 130 seconds after that main operation mode is displayed 1 3 CHANNELS REBOOT To reboot internal channels or one of internal channels it is necessary...

Страница 7: ...ayed WORK COMPLETION REBOOT POWER OFF After menu REBOOT selection the following message is displayed WORK COMPLETION CONTROLLER REBOOT This message means reboot is in Reboot mean time is 3 5 s after w...

Страница 8: ...8 MRBP 424321 001G2 Version 1 0 15 06 2020 After menu POWER OFF selection turning off window is displayed Power off mean time is 3 5 s after which the control unit display blinks off and sensors pow...

Страница 9: ...el settings Current time New contingency icon disappears after new record review in the contingencies menu Data exchange with the control unit via RS 485 icon disappears in 5 seconds after data exchan...

Страница 10: ...AUTO THRESHOLD 2 RESET AUTO CL CONNECTION PASS 2wires CURRENT mA 4 000 In the top left corner is the channel number and sensor item tag hereunder is the present channel information To return to the ma...

Страница 11: ...ngencies summary for the controller REBOOT controller EMI SSD 1M reboot by the user TURN OFF EMI SSD 1M control unit turn off by the user TURN ON EMI SSD 1M control unit turn on CONTINGENCIES ARCHIVE...

Страница 12: ...DISPLAY 12 MRBP 424321 001G2 Version 1 0 15 06 2020 MEASUREMENT RANGE EXCEEDED measurement range exceeded CL SHORT CIRCUIT channel current loop short circuit Contingencies more detailed description i...

Страница 13: ...OMMUNICATION communication parameters selection DISPLAY display parameters selection ACCESS access settings CONTINGENCIES ARCHIVE CLEARING contingencies archive clearing DEFAULT SETTINGS factory defau...

Страница 14: ...of the display COMMUNICATION means that the values of the network address and or rate have been changed To apply and save the set values it is necessary to select SAVE The asterisk on the top line di...

Страница 15: ...yed channel in the main operation mode auto change time interval set BRIGHTNESS display brightness settings The appearance of an asterisk in the upper line of the display DISPLAY means that the settin...

Страница 16: ...using the buttons and 4 3 1 BRIGHTNESS Display brightness change from 1 to 100 Edited category is chosen by using the buttons and The parameter is changed by using the buttons and 4 4 ACCESS SETTINGS...

Страница 17: ...d Value is changed by using the buttons and To apply and save the password it is necessary to select SAVE and push the button After successful saving of the new password the message is displayed CHANG...

Страница 18: ...HIVE CLEARING CLEAR CONTINGENCIES ARCHIVE CANCEL CLEAR CONTINGENCIES ARCHIVE In the CONTINGENCIES ARCHIVE CLEARING it is possible to confirm or cancel contingen cies archive clearing 4 6 DEFAULT SETTI...

Страница 19: ...ULTS The number of the channel is shown in the top left corner of the display C1 C8 In the SETTINGS menu it is possible to set change the following channel settings MAINTENANCE maintenance mode switch...

Страница 20: ...UREMENT UNIT LFL MIN VALUE 0 0 MAX VALUE 100 0 BLANKING ZONE 1 0 THRESHOLD 1 VALUE 10 0 THRESHOLD 1 HYSTERESIS 0 0 THRESHOLD 1 RESET AUTO THRESHOLD 2 VALUE 20 0 THRESHOLD 2 HYSTERESIS 0 0 THRESHOLD 2...

Страница 21: ...reset method selection Blanking zone thresholds and hysteresis detailed description is shown in the Appendix E The appearance of an asterisk in the upper line of the display CONFIGURATION means that t...

Страница 22: ...rrectly Generally the channel switches to Detector breakout mode 5 2 2 POSITION Edited category is chosen by using the buttons and The category is changed by using the buttons and 5 2 3 GAS TYPE In th...

Страница 23: ...hen in the ACCURACY menu select the appropriate one 5 2 5 MIN VALUE MAX VALUE BLANKING ZONE Edited category is chosen by using the buttons and The category is changed by using the buttons and 5 2 6 TH...

Страница 24: ...e Manual threshold reset is carried out by using handshaking button Automatic reset is carried out after current concentration value decreasing below threshold level Notice If threshold is exceeded on...

Страница 25: ...e top line disappears after saving the set configuration parameters Notice While analog input calibration it is necessary to select current loop connection method that is used hereinafter while detect...

Страница 26: ...GS CANCEL APPLY APPLY AND SAVE In the CALIBRATION SETTINGS menu it is possible to apply and save channel calibration factory default Notice In case of selecting apply without save previous calibration...

Страница 27: ...INTERNAL CHANNELS SETTINGS 27 MRBP 424321 001G2 Version 1 0 15 06 2020 6 EXTERNAL CHANNLES SETTINGS Under development...

Страница 28: ...t all channels factory default it is necessary to enter MENU CHANNELS SET TINGS CHANNELS FACTORY DEFAULT INTERNAL CHANNELS INT CHANNELS FACTORY SETTINGS CONFIGURATION SETTINGS CALIBRATION SETTINGS CON...

Страница 29: ...L APPLY AND SAVE In the INTERNAL CHANNELS CALIBRATION SETTINGS menu it is possible to apply and save channels calibration factory default 7 1 3 CONFIGURATION AND CALIBRATION SETTINGS INT CH CONF AND C...

Страница 30: ...s and channel status archive record on SD card SD CARD INFORMATION storage capacity The appearance of an asterisk in the upper line of the display ARCHIVING SETTINGS means that the settings have been...

Страница 31: ...TION SD CARD INFORMATION STATUS CONNECTED STORAGE CAPACITY 3049 Mb AVAILABLE MEMORY 1 Mb SD CARD INFORMATION menu is an informative SD card data window that contents STATUS SD card connection status S...

Страница 32: ...TWARE VERSION 1 0 1 SOFTWARE DATE 01 01 2020 SOFTWARE TIME 12 00 00 OPERATION TIME d 1 Hh mm ss 02 05 00 In the DEVICE INFORMATION menu the following information is displayed SERIAL NUMBER controller...

Страница 33: ...window is displayed Then program Loader menu is displayed where the following actions may be performed SOFTWARE UPDATING controller software version updating RESET TO FACTORY DEFAULT channels and cont...

Страница 34: ...following message is displayed SOFTWARE FILES SD CARD NOT FOUND 10 2 CHANNELS AND CONTROLLER SETTINGS RESET TO FACTORY DEFAULTS To reset all control unit EMI SSD 1M settings to factory defaults it is...

Страница 35: ...plete program Loader work it is necessary to press the button WORK COMPLETION QUIT THE LOADER REBOOT POWER OFF In the WORK COMPLETION menu it is possible to select one of the actions QUIT THE LOADER q...

Страница 36: ...36 MRBP 424321 001G2 Version 1 0 15 06 2020 Appendix A EMI SSD 1M menu structure...

Страница 37: ...37 MRBP 424321 001G2 Version 1 0 15 06 2020...

Страница 38: ...38 MRBP 424321 001G2 Version 1 0 15 06 2020...

Страница 39: ...39 MRBP 424321 001G2 Version 1 0 15 06 2020...

Страница 40: ...off Internal channels settings Maintenance mode off CL connection type disconnected Position Gas methane Measurement units LFL Minimal concentration value 0 Maximal concentration value 100 Blanking z...

Страница 41: ...e CH4 LFL 100 0 10 0 20 0 3 Propane C3H8 LFL 100 0 10 0 20 0 4 Carbon dioxide CO2 vol 2 50 1 00 2 00 5 Ethane C2H6 LFL 100 0 10 0 20 0 6 Butane 4 10 LFL 100 0 10 0 20 0 7 Isobutane i 4 10 LFL 100 0 10...

Страница 42: ...n cyanide HCN ppm 30 0 1 9 9 9 33 Hydrogen H2 vol 2 00 0 10 0 40 34 Diesel fuel DT LFL 100 0 10 0 20 0 35 Methanol LOC 3 ppm 200 0 11 2 22 5 36 Hydrogen fluoride HF ppm 10 0 2 0 4 0 37 Hydrogen chlori...

Страница 43: ...m 50 0 5 0 10 0 54 Carbonyl chloride COCl2 ppm 1 00 0 60 0 80 55 Methylmercaptan CH3SH ppm 10 0 4 0 8 0 56 Ozone O3 ppm 25 16 21 57 Bromine Br2 ppm 5 0 1 0 2 0 58 Formaldehyde CH2O ppm 10 0 1 0 2 0 59...

Страница 44: ...off off NC NC NC No power supply or the device failed DISPLAY TURNED OFF no flashes every 1 s off NC NC NC Device turned off by the user no on off NC NC NO No tuned channels No power supply on pins X1...

Страница 45: ...range ex ceeding no on off NC NC NO Channel maintenance mode enabled Short circuit in the channel supply circuit Channel power supply disconnected It is necessary to eliminate short circuit cause and...

Страница 46: ...NC Current in the current loop circuit exceeds 31 mA It is necessary to eliminate short circuit in the current loop circuit cause after that the chan nel resumes work in main operation mode au tomatic...

Страница 47: ...ormed automatically after measurand de creasing below thresholds 1 and 2 taking ac count of hysteresis In case of threshold 2 manual reset settings it is necessary to press the button constant frequen...

Страница 48: ...e minimal value 0 blanking zone 5 On figure E 1 before the point 1 and after the point 2 value of the detector equal 0 set minimal value as they are below blanking zone value In the interval from the...

Страница 49: ...Threshold 2 value hysteresis 2 value then relay Threshold 2 returns to initial condition common contact 2 closes to NC contact 3 Example threshold 1 value 10 hysteresis 1 value 3 On figure E 2 before...

Отзывы: