SL-014 v1.6 Page9
Document Ref: SL-014 v1.6
User LED Addr 109
User LED Addr 110
User LED Addr 111
User LED Addr 112
User LED Addr 113
Note that addressable inputs and outputs on
the hub card and display are on Highway 0
Power LED
General Alarm LED
System Fault LED
Battery Backup LED, RED on Battery
E-Stop Button Address 4
Light ring:
GREEN:
Normal
RED:
Alarm
DARK BLUE: Warmup
Light Blue:
Menu
Amber: Fault
T635 PLUS Control Panel & 2 Wire Hub Controller PCB Features
& I/O Addresses
1=STOP
0.00
2=KEY
0.00
4=STOP
0.00
5=CH4
0.00%LEL
Panel Sounder Addr 107
After warm up the display will sequentially indicate each detector. The
detector channel number is shown along with gas type, units and level.
The first channel is always digital input 1. By default this is labelled
‘STOP’ for an emergency stop input, but can be changed. Input 2 is
digital input 2, labelled ‘KEY’. Input 3 is the onboard sensor input which
is by default, disabled. As such this channel does not display on
screen. Channel 4 is then the on-board E-STOP on the display.
The first detector channel cabled to the detector highway port is
channel 5.
Any other channels ‘found’ during installation are sequentially
numbered from 5 onwards.
Note that channel numbers are related to detector addresses. This can
be seen by downloading using the WiFi feature, the panel setup.
Reading the Display