background image

SL-014 v1.6 Page3

 

Document  Ref: SL-014 v1.6

Brief Introduction

The Tocsin 635 series control panels use the latest technology 2-wire addressable highways to 
control gas detectors and associated accessories.  Providing an extremely flexible and low cost 
solution.

Main Features

635 Series
Up to 32 Detector Nodes
Jog Wheel Interface
RGB Backlit Display

Service & Maintenance

It is recommended that control panels and all connected detectors are commissioned upon 
installation and serviced every 6 months by an IGD trained technician.  IGD can offer full training to 
enable your staff to do the servicing or offer a competitive service from our fleet of service 
engineers. 

Warnings and Performance Statements

This control panel is not to be located in a classified Ex area, devices installed in an Ex area 
can be connected to this unit but shall be protected with one of the types of protection 
listed in IEC 60079-0 corresponding to their own category.  

We recommend users read the 

procedures described in IEC 60079-29-2 for reference.

This product must be earthed in accordance with local safety regulations.  A switch or circuit 
breaker must be included in the installation; it must be suitably located; easily reached and it must 
be marked as the disconnect device for the equipment.

The Control Panel leaves the factory configured for the supply voltage stated on the customers order.
Standard options are indicated in the basic specifications on page 4

Should the control panel be used in conjunction with portable generating equipment, care should be 
taken to ensure that the electrical supply is within the tolerance band described above.

°

°

The control panel may be stored at temperatures between -25 C and 60 C. If stored at low 
temperatures and then brought into a warmer environment care should be taken to ensure that  
condensation does not form or enter critical electrical components, for example the power supply. 
Allow 24 hours to stabilise extremes of temperature.

o

The Control Panel is designed to operate  within specification for ambient temperature between -20 C 

o

and  55 C, relative humidity up to 90% ( non-condensing ). Sensor specifications may differ.

Do not use a Control Panel for protection applications that has not been calibrated. If calibration seals 
are missing from the control panel or have been tampered with or broken, then the control panel  must 
be re-calibrated and sealed by a trained engineer.

Substances and interfering gases can cause adverse effects on the performance or electrical safety of 
the gas detection systems. Care should be taken to limit exposure to these poisoning substances, for 
further advice and information contact head office

The response time of the entire system is determined by the time of response of all the parts of the 
equipment within the gas detection system.

The  relationship  between  the  output  signal  and  the  gas  concentration  is  linear,  the  control  panel 
interprets the signal and the gas level is displayed on the RGB backlit display.  IGD hold evidence of 
this linear performance which is available upon request.

Содержание TOC 635 PLUS

Страница 1: ...f e t y I n s t r u c t i o n M a n u a l V 1 6 Images for illustration only see specification within for dimensions and labelling Addressable 2 Wire Document Ref SL 014 v1 6 Operation Manual Control...

Страница 2: ...0 12 13 13 15 20 23 25 25 26 28 29 30 Highway Hub Controller Overview Relay Card Overview Relay Card Setup Special Status States Overview User Actions Menu overview Putting Into Service New Setup Sequ...

Страница 3: ...ations on page 4 Should the control panel be used in conjunction with portable generating equipment care should be taken to ensure that the electrical supply is within the tolerance band described abo...

Страница 4: ...230V AC 50 60Hz 57W Full Load ABS 2 Lines x 8 Digit LCD Display Multi Colour Backlight Red Alarm Yellow Fault Blue Normal IGD Jog Wheel Option Select Alarm Reset RGB 3 off SPCO Relays 4A Non Inductiv...

Страница 5: ...ing and calibrating Incorrect application of gases can a ect calibration results 3 Use equipment and gases traceable to a national standard Any calibration will only be as good as the equipment and ma...

Страница 6: ...es sequentially wired Power can be taken from system modules for small current devices such as LED beacon sounders and is limited to 100mA per module Highways are fused at 2A observe load calculations...

Страница 7: ...n poor performance and or damage to system components 2 WIRE SYSTEMS 2 W i r e G a s D e t e c t i o n S y s t e m I n s t a l l e r s G u i d e V x x OLIVER IGD Triton House Crosby Street Stockport S...

Страница 8: ...S 232 Sensor Port 2 Inputs for E stops Fire 1 off 2 Wire Ports Supporting 32 Addressable Devices 1 off 2 Wire Ports Supporting 8 Addressable Devices L1 L1 L2 L2 Not Fitted Not Fitted Not Fitted Not Fi...

Страница 9: ...e display will sequentially indicate each detector The detector channel number is shown along with gas type units and level The rst channel is always digital input 1 By default this is labelled STOP f...

Страница 10: ...event logs download and edit the controllers setup generate the panel production test certi cate and more Please refer to IGD s on line Note Iphones can be slow to connect depending on setup Turning...

Страница 11: ...ted to the controller If you want to edit off line then you must rst save the panel setup Use the enclosed QR code to access the remote web portal You can then upload the panel setup and edit off line...

Страница 12: ...OWN BUTTON UP BUTTON Each Addressable relay card must have its own unique base address This can be set on the card and is indicated below The relays are then addresses numbered from that base address...

Страница 13: ...t Relay on The Card relays number from this one Base Address set up LED s and interface for the relay card In all Cases Relay contact ratings 5A 250V AC Non Inductive 5A 30V DC Non Inductive Spike sup...

Страница 14: ...ay cards also have analogue and digital inputs that can be used to read data onto the system from external devices Setup of the inputs type range addressing etc is controlled via IGD s Android Apps Wi...

Страница 15: ...l Modbus State Available Fault Relay Active Alarm Relays Normal Modbus State Available Fault Relay Active Alarm Relays Normal Modbus State Available Fault Relay Active Alarm Relays Normal Modbus State...

Страница 16: ...ill not be possible to reset the alarm The sounder re instates if the next alarm level is breached Once fully installed the TOC 635 controller will continuously monitor connected gas detectors and sen...

Страница 17: ...ed Selector Button Menu Jog Wheel and Status Light Ring WARMUP 600s Initial power up sequence is o Indicate board tested status end user should see PASSED with a green backlight o Display then shows S...

Страница 18: ...ise to decrement With the correct password displayed press the centre selection button to go to the menu or function Current Channel Reading Inhibit the control panel for up to 60 minutes Use this opt...

Страница 19: ...his option to ZERO connected devices Use this option to CALIBRATE connected devices Set alarm Level 1 Set alarm Level 2 Set alarm Level 3 Set alarm Level 1 Type Set alarm Level 2 Type Set alarm Level...

Страница 20: ...devices Use this option to CALIBRATE connected devices Set alarm Level 1 Set alarm Level 2 Set alarm Level 3 Set alarm Level 1 Type Set alarm Level 2 Type Set alarm Level 3 Type Set Relay to Mutable N...

Страница 21: ...tions Provides access for control panel set up and diagnostic functions Use this option to Reset the Hubcard System Re boot Reset Hubcard to defaults Display Self Test Not Used Use to Move to the Engi...

Страница 22: ...kits are available and necessary to perform calibration and bump testing Record all results for traceability find sen 1 of 12 find rly 1 of 12 zero 1 of 15 cal 2 of 15 Putting Into Service Note that...

Страница 23: ...unication The following diagram shows the three main terminal PCB types for detectors and I O interface nodes and the relevant check points Warm Up Period With sensors connected and after the TOC 635...

Страница 24: ...ommunicating correctly Allow at least 1 hour for the detectors to correctly warm up and stabilise During this period if the relay outputs are being used check the cabling then plug in and test using t...

Страница 25: ...on then works in the following manner Press and hold button until prompted to release The system starts discovering connected devices Display indicates devices found so far Display indicates progress...

Страница 26: ...save and view Events stored on the controller Events saved are time and date stamped and are triggered by Power on Fault Condition Alarm 1 Condition Alarm 2 Condition Alarm 3 Condition Mute Reset Ala...

Страница 27: ...te This type of alarm is typically used in safety applications for Oxygen deficiency monitoring where you are monitoring for a falling Oxygen level Press and hold until prompted to release to select t...

Страница 28: ...nloads section of the IGD website The enclosed sample document is for indication only levels will change as new guidance is issued by governing authorities The following should be noted 1 At least Ala...

Страница 29: ...f the zero and calibration points are within 2 of range then take no further action zeroing and calibrating a detector that already reads correctly will not improve its performance If either is out th...

Страница 30: ...portable detector B Use a suitable ZERO gas as follows Zero gas should have a humidity between 0 90 RH GAS RECOMMENDED ZERO GAS O2 CO2 NITROGEN PELLISTOR INSTRUMENT AIR TOXIC GASES NITROGEN The follow...

Страница 31: ...ads When carrying out a zero or calibration the controller sends the request to the detector head for action and monitors the result This means that detectors can be supplied pre calibrated The readin...

Страница 32: ...ollows MODBUS INTERNAL MEMORY MAP ADDRESSES COMMAND STRUCTURE Parameter Setting 1 Modbus Mode RTU Mode Only 2 Operating Mode Slave Mode Only 1 3 Response Time Maximum 100mS 5s for Zero Command 4 Reque...

Страница 33: ...1 to 999 Bit0 AL1 Bit1 AL2 Bit2 AL3 Bit3 Fault Bit4 Sensor Disabled Bit5 Sensor Fault Bit6 Under Range Fault Bit7 Over Range Fault Bit8 Comms Fault Bit9 Spare Bit10 Spare Bit11 Spare Bit12 Spare Bit13...

Страница 34: ...Failed Self Test Processor Voltage Fault Failed Self Test Flash Memory Fault Failed Self Test RAM Indication On Screen Count Down Blue Comms Error Displayed Yellow Channel Display Indication Yellow C...

Отзывы: