26
IGBT D
IMMER
R
ACKS
Installation
& Operation
I
NSTALLING
D
IMMER
M
ODULES
Capio Plus Dimmer Modules are easy to slide in place without tools. Please do not insert modules until your installation is ap proved
by an Lightolier Controls® technician.
1. Make sure that the circuit breakers are off and their latch is pushed to the right.
2. Insert the edges of the dimmer module circuit board into the right and left guides ( Figure 22 ).
3. Push the module in until the alignment pins at the back seat firmly into the connector on the dimmer back plane, and the dimmer is
seated firmly against the metal frame of the rack.
4. Slide the circuit breaker handles and their latch to the left, and into the slot in the frame of the rack.
: If you are installing modules of different types, please consult system drawings for the placement order. Modules of different
power ratings are keyed to prevent improper insertion.
: To remove modules, turn circuit breakers off and slide the latch to the right before pulling module straight out.
Installing Dimmer and Control Modules
Figure 22: Dimmer Module Insertion
Dimmer card
entering guide
Circuit breakers
Circuit breaker latch
Do not energize the Capio
Plus IGBT Dimmer Rack until the wiring has been approved by a technician from Philips Lighting Controls. Contact Technical
Support at +1-866-526-2731 to arrange for approval. Refer to page 53.