4
• Only use the product for its intended purpose
�
• Only use the product for permissible media
�
• If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur�
• The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator�
• Installation, electrical connection, set-up, operation and maintenance of the
product must be carried out by qualified personnel authorised by the machine
operator�
• Protect units and cables against damage�
3 Getting started
1� Connect unit to PC to set the parameters via the IO-Link interface�
2� Set the standard unit of measurement�
-[Uni]: °C or °F
3� Set analogue signal�
-[OU2]: I = 4���20 mA or I neg = 20���4 mA
-[ASP] and [AEP]: scaling of the measuring range�
4� Set drift monitoring�
-[drW]: drift threshold from which the unit signals "warning"�
-[drA]: drift threshold from which the unit signals "alarm"�
-[ddr]: delay time of the drift detection�
5� Select diagnostic cases that should be signalled
-[drEd]:
ON = only diagnostic cases of category "failure"
ONdr = diagnostic cases of categories "alarm" + "failure"
OFF = diagnostic cases of categories "warning" + "alarm" + "failure"
6� Configure analogue signal for diagnostic case
-[FOU2]: On = 21�5 mA or OFF = 3�5 mA