12
Diagnostic messages
Diagnos-
tic cases
[drEd] Output
Warning
Alarm
Failure
= ONdr
Analogue output
●
6���9
Switching output*
●
●
3���9
= OFF
Analogue output
●
6���9
Switching output*
●
●
●
1���9
Table 3: Setting of diagnostic cases to be signalled (3-wire operation)
* physical switching output as well as a switching output simulated via IO-Link�
Since all diagnostic cases can be signalled via the switching output
in 3-wire operation, the analogue output only leaves its measured
temperature value in diagnostic case of category "failure"� This ensures
maximum use of the analogue output�
The parameter [dOU1] is used to define how the diagnostic output reacts to
diagnostic messages:
Normal
Diagnostic message
[dOU1]
Warning
Alarm
Failure
= nc
normally closed
= nc+
normally closed,
extended
2 Hz
= no+
normally open,
extended
2 Hz
= Hb
heartbeat
4 Hz
2 Hz
Table 4: Switching signal in diagnostic case