SU2020 SU8020 SU2021 SU8021 SU2621 SU8621
Ultrasonic flow meter
46
10.5.6.2 Parameter setting via IO-Link: display colour setting
u
Call up [Parameters] > [Display Setting].
u
Select [coL.F] and choose the font colour for the flow value:
•
Colour: [bk/wh], [red], [green], [yellow]
•
Colour change: [r-cF], [G-cF]
When a colour change is configured, set the upper and lower flow limits: Select [Parameter] >
[Display settings] > [Window for colour change] > [Flow] and set [cFH.F] and [cFL.F].
u
Select [coL.T] and choose the font colour for the temperature value:
•
Colour: [bk/wh], [red], [green], [yellow]
•
Colour change: [r-cF], [G-cF]
When a colour change is configured, set the upper and lower temperature limits: Select
[Parameter] > [Display settings] > [Window for colour change] > [Temperature] and set [cFH.T]
and [cFL.T].
u
Select [coL.V] and choose the font colour for the totaliser value:
•
Colour: [bk/wh], [red], [green], [yellow]
10.6 Diagnostic functions
The unit offers a range of diagnostic functions.
Diagnostic messages can be provided via an output signal. See also
.
This chapter describes diagnostic functions that provide information but not an output signal.
10.6.1 Read totaliser values
For the totalisers Vol.1 and Vol.2, the following values can be read at any time:
•
current volumetric flow quantity (= consumed quantity since the last reset).
•
consumed quantity before the last reset.
•
time in minutes since the last reset.
For the totaliser Vol.L, the following values determined during the entire operating time can be read at
any time:
•
volumetric flow quantity in preferred direction (= positive flow direction).
•
volumetric flow quantity in non-preferred direction (= negative flow direction).
10.6.1.1 Reading via unit keys: totaliser values
u
Go to the [EF] > [TOTL] menu.
u
Select [Vol.x] and read consumption values.
10.6.1.2 Reading via IO-Link: totaliser values
u
Select [Parameter] > [Totaliser].
u
Select [Vol.x] and read consumption values.
10.6.2 Memory
The unit stores the maximum and minimum measured process values.