Mechatronic flow sensor
SBY2xx SBG2xx SBN2xx
23
u
Select [diS] and set the update rate and orientation of the display:
•
d1, d2, d3: update of the measured values every 50, 200, 600 ms.
•
rd1, rd2, rd3: display as with d1, d2, d3; rotated by 180°.
•
OFF: The process value display is deactivated in the RUN mode.
The LEDs remain active even if the display is deactivated. Error messages are displayed even if
the display is deactivated.
10.2.4.2 Display colour setting
u
Select the DIS menu.
u
Select [coLr] and define the colour of the characters in the process value display:
•
rEd: red
•
GrEn: green
•
rxou: colour change from green to red
•
Gxou: colour change from red to green
10.2.4.3 Medium
u
Select the CFG menu.
u
Select [MEdi] and set the medium:
•
H2O: Water
•
OIL:
Ò
Technical data sheet at
•
OIL2:
Ò
10.2.4.4 Output logic
u
Select the CFG menu.
u
Select [P-n] and set PnP or nPn.
10.2.4.5 Measured value damping for switching output
u
Select the CFG menu.
u
Select [dAP] and set the damping constant in seconds (τ value 63 %).
10.2.4.6 Measured value damping for analogue output
u
Select the CFG menu.
u
Select [dAA] and set the damping constant in seconds (τ value 63 %).
10.2.4.7 Error behaviour of the outputs
u
Select the CFG menu.
u
Select [FOUx] and set the error behaviour for OUTx:
•
Switching output
– On: Output switches ON in case of a fault.
– OFF: Output switches OFF in case of a fault.
– OU: Output switches irrespective of the error as defined with the parameters.
•
Analogue output
– On: The analogue signal goes to 22 mA.
– OFF: The analogue signal goes to 3.5 mA.