background image

Mechatronic flow sensor

SBY2xx SBG2xx SBN2xx

21

10.2 Parameter setting via the unit keys

CAUTION

If the medium temperature is above 50 °C (122 °F), parts of the housing can increase in
temperature to over 65 °C (149 °F).

w

Risk of burns

u

Do not touch the device with your hands.

u

Use another object (e.g. a ballpoint pen) to carry out settings on the unit.

10.2.1 Parameter setting in general

Intention

Action

Change from the process value display to the main menu

[●]

Change to the submenu

Use [▼] to navigate to the sub-
menu (e.g. EF), then [●]

Select the requested parameter

[▲] or [▼]

Change to the setting mode

[●]

Modification of the parameter value

[▲] or [▼] > 1 s

Apply the set parameter

[●]

Exit parameter setting without saving

[▲] and [▼]

Return to the next higher menu level
(repeat several times to reach process value display)

[▲] and [▼]

Return to the process value display

> 30 seconds (timeout)

The unit keys can only be locked via the IO-Link interface. Unlocking is then only possible via
IO-Link.

10.2.2 Presets

Before setting the parameters, first check the following default settings and change them if
necessary:

- [SEL1]: Process value for OUT1

- [SEL2]: Process value for OUT2

- [uni]: Standard unit of measurement for flow

10.2.2.1 Process value for OUTx

u

Select the CFG menu.

u

Select [SELx] and set the process value for output x:

FLOW: Flow

TEMP: Temperature

10.2.2.2 Standard unit of measurement

u

Select the CFG menu.

u

Select [uni] and set the unit of measurement for the flow: l/min, m

3

/h (SBN2xx: gpm, gph).

The selectable units depend on the respective device.

GB

Содержание SBY2 Series

Страница 1: ...Operating instructions Mechatronic flow sensor SBY2xx SBG2xx SBN2xx 11368302 00 06 2021 GB...

Страница 2: ...0 Parameter setting 20 10 1 Parameter setting via IO Link 20 10 1 1 Identification 20 10 1 1 1 Application Specific Tag 20 10 1 2 Parameters 20 10 1 2 1 Access locks to the units Local parameter setti...

Страница 3: ...ding minimum values maximum values 24 11 Operation 25 11 1 Process value display 25 11 2 Reading the parameter setting 25 12 Troubleshooting 26 12 1 Error messages 26 13 Maintenance repair and disposa...

Страница 4: ...aging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or...

Страница 5: ...stem Read this document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without an...

Страница 6: ...r glycol solutions industrial oils coolants It detects the process categories volume flow volumetric flow quantity time and medium temperature ATTENTION Frost formation of the medium w The sensor may...

Страница 7: ...2 selection options Switching signal flow Switching signal temperature Analogue signal flow Analogue signal temperature 4 3 Switching output OUTx changes its switching status if it is above or below t...

Страница 8: ...a fault can be set via the parameter FOU 4 4 Analogue output The unit provides an analogue signal of 4 20 mA proportional to the process value If the measured value is outside the measuring range or...

Страница 9: ...equency signal in Hz that is provided when the upper measured value MEW or FEPx is reached The measuring range is scalable FSPx defines the lower measured value from which a frequency signal is provid...

Страница 10: ...haracteristics frequency output temperature 1 Frequency signal FSP1 Frequency start point 2 Temperature FEP1 Frequency end point 3 Display range FRP1 Frequency signal Hz for upper measured value 4 Mea...

Страница 11: ...ng with sensors and actuators General information about IO Link can be found at io link ifm IO Device Description IODD with all parameters and process data of the unit can be found at documentation if...

Страница 12: ...oid major changes of cross section on the inlet side u Fit the unit in the pipe in accordance with the flow direction arrow and tighten at the spanner flats Do not clamp the housing in a vice IN OUT F...

Страница 13: ...ttom side of the unit Information about available accessories at www ifm com 5 4 Installation in case of medium containing dirt u Use a 200 micron filter in front of the inlet IN u Install sensor hori...

Страница 14: ...iring diagram colours to DIN EN 60947 5 2 BK black BN brown BU blue WH white Pin Assignment 1 L 3 L 4 OUT1 Switching signal flow Switching signal temperature Frequency signal flow Frequency signal tem...

Страница 15: ...nts 1 3 4 2 5 Fig 14 Operating and display elements 1 Switching status LED for OUT1 2 Switching status LED for OUT2 3 Process value in the indicated unit of measurement 4 4 digit alphanumeric display...

Страница 16: ...igate from the process value display to the main menu and from there to the submenus Process value display Main menu Extended functions EF Basic settings CFG Display settings DIS Min max memory MEM Fi...

Страница 17: ...functions EF menu ou2 Hno Hnc Fno Fnc I P n dAP dAA SEL1 SEL2 EF CFG FLOW TEMP FLOW TEMP nPn PnP 0 1 0 ou1 Hno Hnc Fno Fnc FRQ uni m3h Lmin GPH GPm FOU1 FOU2 OFF On OU OFF On OU MEdi OIL H2O OIL 2 Fig...

Страница 18: ...SBY2xx SBG2xx SBN2xx Mechatronic flow sensor 18 EF DIS coLr SELd FLOW TEMP GrEn rEd diS d2 d3 d1 rd1 rd2 rd3 OFF r1ou G1ou r2ou G2ou Fig 20 Display settings DIS menu...

Страница 19: ...nctions and generates output signals according to the set parameters During the power on delay time the outputs are switched as programmed OFF with normally open function Hno Fno OFF with normally clo...

Страница 20: ...es on parameter setting Manual of the parameter setting software List of all available parameters in the PDF IO Link interface description at documentation ifm com Via IO Link all parameters can be se...

Страница 21: ...r Exit parameter setting without saving and Return to the next higher menu level repeat several times to reach process value display and Return to the process value display 30 seconds timeout The unit...

Страница 22: ...mally open Fnc window function normally closed u Select the main menu u Select FHx and set the upper limit of the window section u Select FLx and set the lower limit of the window section 10 2 3 3 Fre...

Страница 23: ...u Select MEdi and set the medium H2O Water OIL Technical data sheet at documentation ifm com OIL2 Technical data sheet at documentation ifm com 10 2 4 4 Output logic u Select the CFG menu u Select P n...

Страница 24: ...mode u Press and simultaneously for 10 s until uLoc is displayed 10 2 4 9 Factory reset u Select the EF menu u Select rES u Briefly press u Keep or pressed w is displayed u Briefly press w The unit ca...

Страница 25: ...er views w After 30 s the unit returns to the standard display 1 2 Fig 21 Process value display 1 Standard display as set under SELd and uni Example SELd FLOW and uni m3 h 2 Further view The LED indic...

Страница 26: ...ameter change rejected u Unlock the unit using the unit keys C Loc Setting buttons on the unit temporarily locked parameter setting via IO Link communication active u Finish parameter setting via IO L...

Страница 27: ...g may be required u Unscrew sensor head u Remove float and spring u Clean the inside of the float spring and housing e g by means of compressed air u Before re assembly check O ring for damage If nece...

Страница 28: ...P1 FH1 TEMP 12 C 54 F rP1 FL1 TEMP 11 C 52 F FrP1 FLOW 10 FrP1 TEMP 10 FSP1 TEMP 10 C 14 F FEP1 TEMP 100 C 212 F FEP1 FLOW 100 SP2 FH2 FLOW 40 rP2 FL2 FLOW 39 SP2 FH2 TEMP 34 C 94 F rP2 FL2 TEMP 33 C...

Отзывы: