10.2.3 Setting the output functions
The parameters for flow monitoring and temperature monitoring are set in the same way. The
prerequisite is that the process value for OUTx has first been defined via [SELx].
10.2.3.1 Limit monitoring OUTx / hysteresis function
u
Select the CFG menu.
u
Select [oux] and set the switching signal:
•
Hno: hysteresis function / normally open
•
Hnc: hysteresis function / normally closed
u
Select the main menu.
u
Select [SPx] and set the measured value at which the output switches.
u
Select [rPx] and set the measured value at which the output switches off.
10.2.3.2 Limit monitoring OUTx / window function
u
Select the CFG menu.
u
Select [oux] and set the switching signal:
•
Fno: window function / normally open
•
Fnc: window function / normally closed
u
Select the main menu.
u
Select [FHx] and set the upper limit of the window section.
u
Select [FLx] and set the lower limit of the window section.
10.2.3.3 Frequency signal OUT1
u
Select the CFG menu.
u
Select [ou1] and set FRQ.
u
Select the main menu.
u
Select [FSP1] and set the lower temperature value at which 0 Hz is provided.
FSP1 is only available for temperature measurement.
u
Select [FEP1] and set the upper measured value at which the maximum frequency is provided.
u
Select [FrP1] and set the maximum frequency in Hz.
10.2.3.4 Analogue signal OUT2
u
Select the CFG menu.
u
Select [ou2] and set the function:
I: flow-proportional current signal 4…20 mA.
10.2.4 User settings (optional)
10.2.4.1 Standard display
u
Select the DIS menu.
u
Select [SELd] and set the standard unit of measurement:
•
FLOW: The display shows the current process value for flow rate.
•
TEMP: The display shows the current process value for temperature.