SBY2xx SBG2xx SBN2xx
Mechatronic flow sensor
20
10 Parameter setting
The parameters can be set via the IO-Link interface or via the keys on the unit.
Parameters can be set before installation or during operation.
If you change parameters during operation, this will influence the function of the plant.
u
Ensure that there will be no malfunctions in your plant.
During parameter setting the unit remains in the operating mode. It continues to monitor with the
existing parameter until the parameter setting has been completed.
10.1 Parameter setting via IO-Link
For parameter setting via the IO-Link interface, you need suitable parameter setting software and the
IO Device Description (IODD) for the unit.
•
IODD, parameter setting software and information on IO-Link at
.
•
Notes on parameter setting
Ò
Manual of the parameter setting software.
•
List of all available parameters in the PDF "IO-Link interface description" at
Via IO-Link, all parameters can be set that are also accessible via the keys on the unit. In addition, the
functions described below are available.
10.1.1 Identification
Information about the unit is provided via the IODD. In addition, customer-specific descriptions
for identification can be assigned to the unit via IO-Link.
10.1.1.1 Application Specific Tag
•
Customer-specific application description.
•
Maximum length 32 characters and freely definable.
10.1.2 Parameters
The unit is configured via the parameters. The parameters described below are only available
via the IO-Link interface.
10.1.2.1 Access locks to the units: Local parameter setting
•
[Open]: The unit can be adjusted using the keys on the unit.
•
[Blocked]: The keys on the unit are locked so that settings on the unit and unlocking can only be
made via IO-Link.