Mechatronic flow sensor
SB1xxx SB2xxx SB3xxx SB4xxx SB5xxx SB6xxx SB7xxx SB8xxx SB9xxx
SB03xx
21
10.3.4 Error behaviour of the outputs
The response of the OUTx output in case of a fault can be set via the parameter [FOUx]. Depending
on the selected output function, the following signals are provided in case of a fault:
•
Switching signal:
– On: The output switches ON in case of a fault.
– OFF: The output switches OFF in case of a fault.
– OU: The output switches irrespective of the fault as defined with the parameters.
•
Analogue signal:
– On: The analogue signal goes to 22 mA.
– OFF: The analogue signal goes to 3.5 mA.
– OU: The analogue signal still corresponds to the measured value.
•
Frequency signal:
– On: The frequency signal goes to 130 % of [FrPx].
– OFF: The frequency signal goes to 0 Hz.
– OU: The frequency signal still corresponds to the measured value.
10.3.4.1 Parameter setting via unit keys: Error behaviour of the outputs
u
Call up the menu [EF] > [CFG].
u
Select [FOUx] and set the error behaviour for OUTx: On, OFF, OU.
10.3.4.2 Parameter setting via IO-Link: Error behaviour of the outputs
u
Call up [Parameters] > [Error Configuration Output x].
u
Select [FOUx] and set the error behaviour for OUTx: On, OFF, OU.
10.4 User settings
The chapter describes setting options for adaptation to the customer-specific application.
10.4.1 Standard unit of measurement
A unit of measurement can be selected with which the process value is shown in the display by
default. All further parameter settings are based on this unit.
Selectable values:
Flow rate: l/min;
m3/h
; gpm; gph.
Temperature: °C or °F.
10.4.1.1 Parameter setting via unit keys: Standard unit of measurement
u
Call up the menu [EF] > [CFG].
u
Select [uni.F] and set the unit of measurement.
u
Select [uni.T] and set the unit of measurement.
10.4.1.2 Parameter setting via IO-Link: Standard unit of measurement
u
Call up [Parameters] > [Display Setting].