4.2  Switching function

OUTx changes its switching state if it is above or below the set switching limits 

(SPx, rPx). The following switching functions can be selected:

• 

Hysteresis function / normally open: [OUx] = [Hno] (→ fig. 1).

• 

Hysteresis function / normally closed: [OUx] = [Hnc] (→ fig. 1).

First the set point (SPx) is set, then the reset point (rPx) with the requested 

difference�
• 

Window function / normally open: [OUx] = [Fno] (→ fig. 2).

• 

Window function / normally closed: [OUx] = [Fnc] (→ fig. 2).

The width of the window can be set by means of the difference between SPx and 

rPx� SPx = upper value, rPx = lower value�



1

2

P = system pressure; HY = hysteresis; FE = window

4.3  Diagnostic function

Output 2 is used as diagnostic output based on the DESINA specification if [OU2] 

= [dESI]�
•  If there is no fault, the output is switched and carries UB+ (if P-n = PnP) or UB- 

(if P-n = nPn)�

• 

In case of malfunctions the output becomes inactive. The following 

malfunctions are detected:

 -measuring cell defective;

 -short circuit in output 1

Содержание PN01 A Series

Страница 1: ...Operating instructions Pressure sensor PN01xA 706232 01 01 2019 UK...

Страница 2: ...setting 10 9 1 Parameter setting in general 10 9 2 Configure display optional 12 9 3 Set output signals 12 9 3 1 Set the output function 12 9 3 2 Set switching limits 12 9 4 User settings optional 13...

Страница 3: ...the compatibility of the product materials with the media to be measured in all applications You can find information about the product materials in the technical data sheet or chapter 12 Technical da...

Страница 4: ...he unit may be destroyed NOTE risk of injury 4 Function 4 1 Communication parameter setting evaluation The unit displays the current process value It generates 2 output signals according to the parame...

Страница 5: ...rmally open OUx Fno fig 2 Window function normally closed OUx Fnc fig 2 The width of the window can be set by means of the difference between SPx and rPx SPx upper value rPx lower value 1 2 P system p...

Страница 6: ...ional and international regulations for the installation of electrical equipment must be adhered to Voltage supply to EN 50178 SELV PELV Disconnect power Connect the unit as follows 2 x positive switc...

Страница 7: ...7 LED 8 switching state of the corresponding output 9 Alphanumeric display 4 digits Display of the current system pressure Indication of the parameters and parameter values 10 Set button Setting of th...

Страница 8: ...8 8 Menu 8 1 Menu structure...

Страница 9: ...Switching signal for the pressure limit values hysteresis function H or window function F either normally open no or normally closed nc Diagnostic signal OU2 dESI EF Extended functions opening of menu...

Страница 10: ...pressing once or scrolling by holding pressed Numerical values are incremented continuously For reducing the value let the display move to the maximum setting value Then the cycle starts again at the...

Страница 11: ...layed here Uni With the user interface of the program ifm Container Activate the EF button If menu level 2 is protected by an access code the input field for the code no is activated Enter the valid c...

Страница 12: ...ng mode 9 3 Set output signals 9 3 1 Set the output function Select OU1 and set the function Hno hysteresis function normally open Hnc hysteresis function normally closed Fno window function normally...

Страница 13: ...also an effect on the display and the IO Link process value The following fixed values can be set they define the switching frequency f of the output dAP 3 6 10 17 30 60 125 250 500 f Hz 170 80 50 30...

Страница 14: ...r another 15 s it returns to the Run mode 10 2 Error indications OL Overload pressure above measuring range UL Underload pressure below measuring range SC1 Short circuit in OUT1 SC2 Short circuit in O...

Страница 15: ...LEDs 3 Programming button 12 Technical data Operating voltage V 18 36 DC1 Current consumption mA 50 Current rating per switching output mA 250 Reverse polarity overload protection up to 40 V Short ci...

Страница 16: ...wetted parts stainless steel 303 1 4305 ceramics FPM Viton Housing material stainless steel 304 1 4301 high grade stainless steel 316L 1 4404 PC Makrolon PBT Pocan PEI FPM Viton Protection rating IP...

Страница 17: ...0 0 dr1 0 0 dS2 0 0 dr2 0 0 P n PnP dAP 60 diS d2 Uni bAr mbAr the indicated percentage of the final value of the measuring range VMR of the respective sensor for PN014 the percentage of the measurin...

Отзывы: