9.4 User settings (optional)
9.4.1 Set delay for the switching outputs
[dS1] / [dS2] = switch-on delay for OUT1 / OUT2.
[dr1] / [dr2] = switch-off delay for OUT1 / OUT2.
►
Select [dS1], [dS2], [dr1] or [dr2] and set a value between 0�2 and 50 s
(at 0�0 the delay time is not active)�
9.4.2 Set output logic for the switching outputs
►
Select [P-n] and set [PnP] or [nPn]�
9.4.3 Set damping for the switching outputs
►
Select [dAP] and set the value�
dAP value = response time between pressure change and change of the
switching status in milliseconds� Damping has also an effect on the display
and the IO-Link process value�
The following fixed values can be set; they define the switching frequency
(f) of the output:
dAP
3
6
10
17
30
60
125 250 500
f [Hz] 170
80
50
30
16
8
4
2
1
9.5 Service functions
9.5.1 Read min/max values for the system pressure
►
Select [HI] or [LO], briefly press [Set]�
Select [HI] = maximum value, [LO] = minimum value�
Delete memory:
►
Select [HI] or [LO]�
►
Press [Set] and keep it pressed until [----] is displayed�
►
Press [Mode/Enter] briefly�
[LO] is only available for PN014A�
9.5.2 Reset all parameters to factory setting
►
Select [rES]�
► Press [SET] and keep it pressed until [----] is displayed.
►
Press [Mode/Enter] briefly�
We recommend noting down your own settings before carrying out a reset
(→ 11 Factory setting).