9.4.3 Setting the delay time for the switching outputs
[dS1] / [dS2] = switch-on delay for OUT1 / OUT2�
[dr1] / [dr2] = switch-off delay for OUT1 / OUT2�
►
Select [dS1], [dS2], [dr1] or [dr2], set value between 0�1 und 50 s (at 0�0
the delay time is not active)
9.4.4 Setting the output polarity
►
Select [P-n] and set [PnP] or [nPn]�
9.4.5 Setting the damping for the switching signal
►
Select [dAP] and set value between 0�01 and 4�00 s (at 0�00 = [dAP] is
not active)�
dAP value = response time between pressure change and change of the
switching status in seconds�
[dAP] influences the switching frequency: f
max
= 1 ÷ 2dAP�
[dAP] also affects the display�
9.4.5 Setting the damping for the analogue signal
►
Select [dAA] and set a value: 0,0 - 0,1- 0,5 or 2,0 s (at 0�0 = [dAA] is not
active)�
dAA value = response time between pressure change and change of the
analogue signal in seconds�
9.5 Service functions
9.5.1 Reading the min./max. values for the system pressure
►
[Select [HI] or [LO], press [Set] briefly�
[HI] = maximum value, [LO] = minimum value�
Delete memory:
►
Select [HI] or [LO]�
►
Press [SET] until [---] is displayed�
►
Press [Mode/Enter] briefly�
10 Operation
After power on of the supply voltage the unit is in the Run mode (= normal
operation)� It carries out its measurement and evaluation functions and generates
output signals according to the set parameters�
Operating indicators
→ 7 Operating and display elements
�