14
• Changing from menu level 1 to menu level 2
►
Press [Mode/Enter] until [EF] is displayed
.
�
►
Press [Set] briefly�
> The first parameter of the submenu is displayed (here: [HI])�
• Locking / unlocking
The unit can be locked electronically to prevent unintentional wrong settings�
►
Ensure that the unit is in the normal operating mode�
►
Press [Mode/Enter] + [Set] for 10 s�
> Indication goes out briefly (acknowledgement of locking / unlocking)�
Units are delivered from the factory in the unlocked state�
With the unit in the locked state [Loc] is indicated briefly when you try
to change parameter values�
• Timeout
If no button is pressed for 15 s while the parameters are being set, the unit returns to
the operating mode with unchanged values�
9.2 Configuring the display (optional)
►
Select [Uni] and set the unit of measurement:
-bAr (= bar / mbar),
-PSI,
-PA (= MPa / kPa)�
►
Select [diS] and set update rate and orientation of the display
-[d1]: Update of the measured value every 50 ms�
-[d2]: Update of the measured value every 200 ms�
-[d3]: Update of the measured value every 600 ms�
-[Ph] = display of the measured peak value remains for a short time
(peak hold)�
-[rd1], [rd2], [rd3], [rPh]: Display like d1, d2, d3, Ph; rotated by 180°�
-[OFF]: The display is deactivated in the operating mode� If one of the
buttons is pressed, the current measured value is displayed for 15 s�
Another press of the Mode/Enter button opens the Display mode� The
LEDs remain active even if the display is deactivated�