Application example:
A = hazardous area
S = minimum safety distance
6.3 Installation of the safety light grids
These versions of OY95xS safety light grids are suitable for access
prevention for entire bodies.
They must not be used for the protection of hands or body parts!
The minimum safety distance (S) is determined using the
following formula:
S = 1600 (t + t
2
) + 850
For more information see ISO 13855 / EN 999.
A = hazardous area
Hx = height
S = minimum safety distance
G = reference level
6.4 Minimum distance between transmitter and receiver
A minimum distance of 8 m between transmitter and receiver has to be
observed. Operation at distances between 0 and 8 m is not permitted!