28
11 Notes on parameter setting via IO-Link
On delivery the LK81xx-type unit is not operational.
First, the integrated overfill prevention OP has to be adjusted.
Depending on the application, OP adjustment can be carried out in diffe-
rent ways:
• directly on the display
.
• via an IO-Link tool (e.g. LR DEVICE), button "Teach_OP [cOP]".
• via the controller: write the value 208 to the IO-Link index 2 (length: 1
byte).
The OP adjustment is not part of the data storage.
Therefore, a simple replacement (e.g. in case of a unit failure) is only possible with
reservations: On the new unit, the OP adjustment has to be carried out manually,
either via the operating keys or via IO-Link. Only when the OP adjustment has
been carried out successfully does the unit revert to the cyclical process data
transmission.
After a factory reset (button "Restore Factory Settings"), the device reboots
and the factory settings are restored.
12 Operation
After switch-on of the operating voltage, the unit is in the operating mode (= nor-
mal operating mode). It carries out its measurement and evaluation functions and
generates output signals according to the set parameters.
►
Check whether the unit operates correctly.
12.1 Operation indication
[----] (continuous)
Initialisation phase after power on.
[numerical value] + LED 1 Current level in cm
[numerical value] + LED 2 Current level in inches
LEDs 5...8
Switching status OUT4...OUT1 (on when the respective
output is switched)
[----]
Level below the active zone.
[FULL] + [numerical value]
alternately
The overflow prevention OP is reached (overflow warning) or
the level is above the active zone.