22
Locking / unlocking:
The unit can be locked electronically to prevent unauthorised setting
(factory setting: not locked).
►
Make sure that the unit is in the normal operating mode.
To lock the unit:
►
Press both buttons simultaneously for 10 s.
> [Loc] is displayed.
To unlock the unit:
►
Press both buttons simultaneously for 10 s.
> [uLoc] is displayed.
The unit can be configured before or after installation.
Exception: To adjust the overflow prevention [cOP], the unit
must
be
installed in the tank.
10.2 Basic settings
Setting ranges of all parameters:
Factory settings of all parameters:
10.2.1 Set unit of measurement [uni]
►
Enter [uni] before entering the values for SPx, rPx, OP or OFS.
This avoids unintentional wrong settings.
►
Select [uni].
►
Determine unit of measurement: [cm], [inch].
uni
10.2.2 Set offset [OFS]
The zone between tank bottom and lower edge of the measuring probe can be
entered as offset value
►
Set [OFS] before entering the values for SPx, rPx or OP.
This avoids unintentional wrong settings.
►
Select [OFS].
►
Set the value for the offset. Note the set unit of measurement [uni].
OFS