31
UK
13.3.2 Definition "from the bottom"
Response level (z) of the overflow prevention OP from the tank bottom is defined.
• Without offset ([OFS] = [0]): [OP] = z - u
• With offset ([OFS] = u):
[OP] = z
Example:
z = 18.0 cm (from the tank bottom), u = 1.0 cm
Without offset: [OP] = 18.0 cm - 1.0 cm = 17.0 cm
With offset: [OP] = 18.0 cm
Round the calculated value to the next lower adjustable value
13.4 Setting ranges [SPx] / [FHx] and [rPx] / [FLx]
Table
12-3
LKx022
LKx023
LKx024
[cm]
[inch]
[cm]
[inch]
[cm]
[inch]
[SPx] / [FHx]
2.5...20.0 1.0...7.8 3.5...39.0 1.4...15.4
6...59
2.5...23.5
[rPx] / [FLx]
2.0...19.5 0.8...7.6 3.0...38.5 1.2...15.2
5...58
2.0...23.0
Step increment
0.5
0.2
0.5
0.2
1
0.5
The values apply if [OFS] = [0].
If [OFS] > [0], they increase by the set offset value.
14 Maintenance / cleaning / change of medium
When removing or installing the unit for maintenance and cleaning:
►
Make sure that the stainless steel tube clip is fixed to the sensor.
> It must be possible to exactly reproduce the installation height and position!
►
Remove the sensor and clean it / carry out maintenance
►
Install sensor exactly in the same position as before.
►
Otherwise check the parameter [OP] and carry out [cOP] once again.