10.3.5 Set reset delay [drx]
►
Select [drx] and set the value between 0.0 and 60 s.
The switch-off delay reacts according to VDMA.
dr1
dr2
10.3.6 Define switching logic [P-n]
►
Select [P-n] and set [PnP] or [nPn].
P-n
10.3.7 Define response of the outputs in case of a fault [FOUx]
►
Select [FOUx] and set value:
FOU1
FOU2
[On] = output switches ON in case of a fault
[OFF] = output switches OFF in case of a fault
A fault is for example: defective hardware, signal quality too low.
Overflow is not considered to be a fault
.
10.3.8 Configure display [diS]
►
Select [diS] and set value:
diS
On
The display is switched on in the operating mode.
Update of the measured values every 500 ms.
[OFF] = The display is switched off in the operating mode. When one of
the buttons is pressed, the current measured value is displayed
for 30 s. The indicator LEDs remain active even if the display is
deactivated.
10.3.9 Reset all parameters to factory settings [rES]
►
Select [rES].
►
Press and hold [Set] until [----] is displayed.
►
Briefly press [Mode/Enter].
> The unit reboots and the factory settings are restored.
rES