21
UK
The unit can be configured before or after installation.
Exception: To adjust the overflow prevention [cOP], the unit
must
be instal-
led in the tank.
10.2 Basic settings
Setting ranges of all parameters:
Factory settings of all parameters:
10.2.1 Set unit of measurement [uni]
►
Enter [uni] before entering the values for SPx, rPx, OP or OFS.
This avoids unintentional wrong settings.
►
Select [uni].
►
Determine unit of measurement: [cm], [inch].
uni
10.2.2 Set offset [OFS]
The zone between tank bottom and lower edge of the measuring probe can be
entered as offset value
►
Set [OFS] before entering the values for SPx, rPx or OP.
This avoids unintentional wrong settings.
►
Select [OFS].
►
Set the value for the offset. Note the set unit of measurement [uni].
OFS
10.2.3 Set medium [MEdI]
►
Select [MEdI] and set the corresponding sensitivity:
MEdI
[CLW.1] = water, hydrous media, coolant emulsions
[CLW.2] = water, hydrous media, coolant emulsions for temperatures >
35 °C (installation in climatic tube)
[OIL.1] = oils with an increased dielectric constant (e.g. some synthetic
oils)
[OIL.2] = oils with a low dielectric constant (e.g. mineral oils)
[Auto] =
automatic medium detection
►
In case of doubt, select [OIL.2] for oils.
►
Check proper function by an application test!