UK
►
Screw the sensor into the respective process connection and tighten it�
Max� tightening torque: 20 Nm
►
After installation, check the tank / pipe for ingress resistance�
6.3 Notes on the use in accordance with EHEDG
The unit is suited for CIP (cleaning in process) when installed
correspondingly�
► Observe the application limits (temperature and material resistance)
according to the data sheet�
►
Make sure that the unit is integrated into the system according to EHEDG�
►
Use self-draining installation�
►
Only use process adapters permitted according to EHEDG with special seals
required by the EHEDG position paper�
►
In case of structures in a tank, the installation must be flush mount� If not
possible then direct water jet cleaning and cleaning of dead spaces must be
possible�
►
The leakage port must be clearly visible and must be installed facing
downwards for vertical pipes�
►
To avoid dead space, install the
sensor in inline housings� Minimum
pipe diameter: 38 mm