10.2.4  Configuration of the switching outputs

With the exception of parameter [P-n], all outputs can be configured separately�

Parameter Value range

Description

P-n

PNP (0),

 

NPN (1)

Output polarity for the 

switching outputs

FOUx

OU (1), 

 

On (2),

 

OFF (4)

Response of OUTx in case 

of a fault�

oux

Hno / hysteresis function, NO (3), 

 

Hnc / hysteresis function, NC (4), 

 

Fno / window function, NO (5), 

 

Fnc / window function, NC (6), 

 

OFF / output off (16)

Output configuration of OUTx�

SPx / FHx 5���95 %

Switch point x in % 

(upper window limit)

rPx / FLx

5���95 %

Switch-off point in % 

(lower window limit)

dSx

0���43200 s

Switching delay for the switch 

point�

drx

0���43200 s

Switching delay for the 

switch-off point�

OUTx 

Counter

0���2000000000

Counts the number of 

switching cycles� Can only 

be read�

10.2.5  Other parameters

Parameter

Value range

Description

Internal temperature

-100���300 °C

Internal temperature of the sensor�

Internal minimum [Lo�T] 

temperature

-100���300 °C

Lowest internal temperature measured�

Internal maximum [Hi�T] 

temperature

-100���300 °C

Highest internal temperature measured�

Power cycles

0���1000000

Number of switch-on operations�

Operating hours

0���500000 h

Number of operating hours�

Minimum memory value 0���100 %

Lowest process value measured�

Maximum memory value 0���100 %

Highest process value measured�

Содержание KQ10 Series

Страница 1: ...Operating instructions Capacitive level sensor KQ10xx UK 80281961 00 02 2020...

Страница 2: ...level edge 10 5 6 2 Signal strength referred to the dynamic range 11 5 6 3 Filling edge sharpness 12 5 6 4 Installation quality 12 5 7 Internal temperature 12 5 8 Switching cycles counters 13 5 9 Oper...

Страница 3: ...25 10 2 4 Configuration of the switching outputs 26 10 2 5 Other parameters 26 10 3 Commands 27 10 3 1 Adjustment of the sensor 27 10 3 2 Setting of the switch points 27 10 3 3 Other commands 28 10 4...

Страница 4: ...d normative requirements to be provided to the operator and user of the system This documentation must contain all necessary information and safety instructions for the operator the user and if applic...

Страница 5: ...continuous process value from 0 100 The sensor detects the medium through the tank wall The wall is suppressed by means of an adjustment function so that only the medium is detected The tank wall must...

Страница 6: ...ation 2 Connect the unit to an IO Link master documentation of the IO Link master software used 3 Carry out an adjustment Empty adjustment 8 1 1 and or full adjustment 8 1 2 Click on Adjust empty tank...

Страница 7: ...respondingly lower signal The unit has 16 capacitive measuring segments 4 They generate measurement signals depending on the degree of coverage 3 200 228 11 11 28 1 2 14 3 4 Fig 1 Measuring range and...

Страница 8: ...ble for sensor sensitivity high and low The high sensitivity level is suited for the detection of low dielectric bulk material for example The low sensitivity level can be used for detection of high d...

Страница 9: ...f the detection range 5 1 Fig 1 In case of the dynamic adjustment the sensor is adjusted to the medium similar to the full adjustment This means that changing the medium without carrying out a new adj...

Страница 10: ...switching output activated in case of events faults switching output deactivated in case of events faults The following events faults are taken into account 10 4 Parameter missing Maintenance required...

Страница 11: ...also be 2 If no level edge can be detected the device decides whether the detection range is completely covered or uncovered based on the application adjustments carried out 8 1 Detection range comple...

Страница 12: ...rrectly detect the level The edge sharpness can only be determined if the medium to be detected is within the measuring range of the unit 5 6 4 Installation quality Relates to the installation quality...

Страница 13: ...parameters The values can be used for orientation after a new start of the unit 5 9 Operating hours counter The number of operating hours can be read from the memory of the unit via IO Link 10 3 3 Oth...

Страница 14: ...y and full adjustment available 8 1 4 Signal strength 15 10 2 3 Index of the level edge is in the detection range 10 2 3 For a correct function of the deposits detection the tank must be free from dep...

Страница 15: ...nces to metal objects If the device is installed with the cable facing upwards the parameter Orientation must be set to Connector on top 10 2 1 Lay the connection cable as straight as possible and do...

Страница 16: ...Installation of several sensors Several units can be mounted head to head or so that they overlap Fig 6 Installation of several sensors Adapt the parameter Orientation according to the installation di...

Страница 17: ...e mounted on bypass pipes with a circular cross section To ensure correct mounting the external diameter of the bypass pipe should be between 5 and 25 mm Fig 7 Installation on bypass pipes When the un...

Страница 18: ...ing from the tank and is done at your own risk The adhesive tape used must not contain any conductive material Fig 8 Installation on the tank The sensor must be flush to the tank Curved flexible tanks...

Страница 19: ...For exchangeable tanks the back of the unit can be screwed to the tank using the E12675 mounting adapter and an M6 screw One screwing point per adapter Fig 9 Installation on exchangeable tanks Maintai...

Страница 20: ...n the medium or tank is changed 6 6 Notes on grounding In order for the unit to function correctly sufficient grounding of the unit as well as of the installation and tank must be ensured 7 Electrical...

Страница 21: ...lication adjustments Do not touch the unit during adjustment After an adjustment there may be increased measurement deviation when the tank is filled or emptied for the first time 8 1 1 Empty adjustme...

Страница 22: ...may change within the valid range Click on Stop dynamic tank adjustment 10 3 1 If no IO Link error occurs the adjustment was successful Event Parameter missing is not indicated any more Empty the tank...

Страница 23: ...ed level is reached Carry out the desired standard command 10 3 2 9 Operating and display elements 1 2 3 4 5 LED Colour Indication green status LED yellow switch point 1 OUT 1 yellow switch point 2 OU...

Страница 24: ...O Link master Follow the menu of the IO Link software Without ifm software parameter setting according to the IODD PDF Set the parameters Check if the parameter setting was accepted by the unit If nec...

Страница 25: ...e Description LED mode All LEDs inactive 0 Only status LED active 1 Only status and switch point LEDs active 2 All LEDs active 3 Activate or deactivate LED indication 10 2 3 Diagnostic parameters Para...

Страница 26: ...lower window limit dSx 0 43200 s Switching delay for the switch point drx 0 43200 s Switching delay for the switch off point OUTx Counter 0 2000000000 Counts the number of switching cycles Can only b...

Страница 27: ...points Besides setting of the switch points via IO Link 10 2 4 the switch point and the switch off point can be set to the currently provided process value Command Description Adjust SPx Sets the swi...

Страница 28: ...Description Device hardware fault Failure 4 The unit does not provide valid measured data due to an internal communication error Short circuit Functional check 3 Short circuit detected on OUT2 or OUT...

Страница 29: ...correct mounting and configuration of the unit If only an empty adjustment or full adjustment has been carried out there may be increased measurement deviation in the detection range when the tank is...

Страница 30: ...structions in 11 3 2 Carry out an empty and full adjustment 8 1 4 If only an empty adjustment is possible Fill the tank until at least one electrode of the measuring range is completely covered Read t...

Страница 31: ...ry correct it 6 6 When used on a bypass pipe Insert the supply cable into the adapter The index of the level edge is in the measuring range However the position significantly deviates from the actual...

Страница 32: ...Low 10 2 1 Carry out a new empty adjustment 8 1 1 If no empty teach has been carried out Check whether the unit has detached from the tank wall Check the installation conditions 6 Carry out a full adj...

Страница 33: ...ription Troubleshooting Deposits above the level Clean the tank s inside in the detection range of the unit 12 Maintenance repair and disposal If used correctly no maintenance and repair measures are...

Страница 34: ...no hysteresis function NO SP1 FH1 25 rP1 FL1 20 ou2 16 OFF Output Off SP2 FH2 50 rP2 FL2 45 ou3 16 OFF Output Off SP3 FH3 75 rP3 FL3 70 Sensitivity 2 Hi High LED mode 3 ALL_On Orientation 0 bottom con...

Страница 35: ...35 UK...

Отзывы: