8 Set-up
On delivery the unit is not operational� First an application adjustment must
be carried out�
After installation and electrical connection, the configuration of the unit can be
changed and adjustments can be carried out�
Changing one of the following parameters will reset the application
adjustment
• Limitation of sensor elements
• Orientation
• Sensitivity
If these parameters are to deviate from the factory settings, they must be
transferred to the unit prior to the application adjustment�
8.1 Application adjustments
Do not touch the unit during adjustment�
After an adjustment, there may be increased measurement deviation when
the tank is filled or emptied for the first time�
8.1.1 Empty adjustment
The inside wall of the tank must be dry/clean during empty adjustment and there
must be no deposits� If this is not possible, only a full adjustment can be carried
out as an alternative�
►
Empty the tank until the level is at least 20 mm below the set detection range�
►
Click on [Adjust empty tank]
�
> If no IO-Link error occurs, the adjustment was successful�
> Event [Parameter missing] is not indicated any more�
> The running light of the LED bar graph goes out�
►
Fill the tank to check whether the unit operates correctly�