UK
Inclination sensor JN
33
14.5 Switching output "window (normally ON; normally closed)" [Fnc]
As compared to the previous output function the output function "window (normally ON)"
only uses inverted logic. Otherwise the behaviour is analogous.
Switching output
On
Off
Angle [°]
Window
rP
e.g. 45 ° → rP = 4500
SP
e.g.: 60 ° → SP = 6000
14.6 Set points SP and reset points rP
The set points SP and reset points rP controlling the output function "ou" can be
freely set within the permissible value ranges.
Set point
Measuring method
Minimum
Maximum
Unit
SP1
Inclination
measurement
-17900
18000
1/100 °
rP1
Inclination
measurement
-18000
17900
1/100 °
SP2
Inclination
measurement
-17900
18000
1/100 °
rP2
Inclination
measurement
-18000
17900
1/100 °
SP1
Vibration measurement 10
32000
1/10 mm/s
rP1
Vibration measurement 0
31990
1/10 mm/s
SP2
Vibration measurement 1
16000
1 mg