![IFM Efector 410 Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/ifm/efector-410/efector-410_device-manual_3905508028.webp)
Inclination sensor JN
28
Index Sub-
index
Type
Value
Content
Read /
Write
Length
586
0
INT16
rP1
for vibration
measurement
v
eff
[1/10 mm/s]
R/W
2
The following parameters can be set for switching output 2 via IO-Link
Index Sub-
index
Type
Value
Content
Read /
Write
Length
532
0
UINT8
FOU2 output 2
in case of a fault
1
→
OU (no fault
indication)
2
→
ON (closed)
4
→
OFF (open)
8
→
TOGGLE (2 Hz)
R/W
1
590
0
UINT8
ou2 output 2
function
3
→
Hysteresis normally
open [Hno]
4
→
Hysteresis normally
closed [Hnc]
5
→
Window normally
open [Fno]
6
→
Window normally
closed [Fnc]
R/W
1
591
0
UINT16 dS2
switching delay
[ms], Step/Round 10
0 ≤ DFO ≤ 10000 8 ms
R/W
2
592
0
UINT16 dr2
switch-off delay
[ms], Step/Round 10
0 ≤ DFO ≤ 10000 8 ms
R/W
2
593
0
INT16
SP1
for inclination
measurement
Angle [1/100 °]
R/W
2
594
0
INT16
rP1
for inclination
measurement
Angle [1/100 °]
R/W
2
4116
0
UINT8
LOGIC_OUT2
logical connective for
switching output 2
0
→
No connective
1
→
Log. OR with output 1
2
→
Log. AND
with output 1
R/W
1
595
0
INT16
SP2
for vibration
measurement
a
peak
[mg]
R/W
2
596
0
INT16
rP2
for vibration
measurement
a
peak
[mg]
R/W
2