UK
Inclination sensor JN
27
Measuring method
Output 1
Output 2
Inclination measurement gimbal
1Y
Index 4106: 0
Index 4100: 3
Gimbal angle Y longitudinal
Gimbal angle Y lateral
Vibration measurement
Index 4106: 1
Vibration velocity v
eff
Vibration acceleration a
peak
The following parameters can be set for switching output 1 via IO-Link
Index Sub-
index
Type
Value
Content
Read /
Write
Length
531
0
UINT8
FOU1 output 1
in case of a fault
1
→
OU (no fault
indication)
2
→
ON (closed)
4
→
OFF (open)
8
→
TOGGLE (2 Hz)
R/W
1
580
0
UINT8
ou1 output 1
function
3
→
Hysteresis normally
open [Hno]
4
→
Hysteresis normally
closed [Hnc]
5
→
Window normally
open [Fno]
6
→
Window normally
closed [Fnc]
R/W
1
581
0
UINT16 dS1
switching delay
[ms], Step/Round 10
0 ≤ DFO ≤ 10000 8 ms
R/W
2
582
0
UINT16 dr1
switch-off delay
[ms], Step/Round 10
0 ≤ DFO ≤ 10000 8 ms
R/W
2
583
0
INT16
SP1
for inclination
measurement
Angle [1/100 °]
R/W
2
584
0
INT16
rP1
for inclination
measurement
Angle [1/100 °]
R/W
2
4115
0
UINT8
LOGIC_OUT1
logical connective for
switching output 1
0
→
No connective
1
→
Log. OR with output 2
2
→
Log. AND
with output 2
R/W
1
585
0
INT16
SP1
for vibration
measurement
v
eff
[1/10 mm/s]
R/W
2