ifm
Basic Device Manual AS-i ControllerE M4 Target V15
2015-10-30
Error description
RTS errors: error codes R01...R46
261
Error message
Cause(s)
Remedy
R29
PC command unknown
Unknown command received in the
operating mode "test mode" of the
device.
► Check the cause of the wrong
command and correct.
R30
PC checksum failure
In the operating mode "test mode" of the
device an invalid checksum was found
in the data flow.
► Configure data flow according to
the specification.
R31
Menu not available
The selected menu could not be
displayed.
Possible causes:
1. Required hardware is not available
in the device
► Check data sheet.
2. Required hardware was not
detected when switching on the
operating system RTS
► Switch the device off and on again.
R32
RTS checksum failure
The checksum of the runtime system
does not correspond to the stored
checksum.
Possible causes:
1. Flash memory faulty
► Replace faulty device.
2. Strong ESD fields with
unacceptable grounding of the
device
► Minimise ESD fields.
► Correct grounding of the device.
R33
Only for AC1353/54
No
ifm
ENET module detected
The requierd Ethernet module could not
be detected.
Possible cause:
faulty device
► Replace faulty device.
R34
Error in font data
The data of the character set is not
correct.
Possible causes:
1. No data is available in the areas
where font data is expected.
► Store the font data at the correct
area.
2. The expected formatting is not
correct.
► Correct the formatting.