Electronic Preset Counter E89005
34
8.6 Tacho/Frequency meter
8.6.1 Input
Submenues for the signal and control inputs�
Display
Description
Submenu
Value
InP.PoL
Input polarity
PnP
PNP: switching to Plus for all inputs in common
nPn
NPN: switching to 0 V for all inputs in common
FiLtEr
Filter for the signal inputs InpA and InpB
oFF
Maximum count frequency
on
Damped to approx� 30 Hz (for control with mechanical contacts)
InPut
Input mode frequency feasurement
A
Simple frequency measurement
Inp A: frequency input
Inp B: no function
ASub b
Differential measurement [A-B]
Inp A: frequency input A
Inp B: frequency input B
AAdd b
Total measurement [A+B]
Inp A: Frequency input A
Inp B: Frequency input B
quAd
Frequency measurement with direction recognition [Quad]
Inp A: Frequency input 0°
Inp B: Frequency input 90°
A / B
Ratio measurement [A/B]
Inp A: Frequency input A
Inp B: Frequency input B
A % b
Percentage differential measurement [(A-B) / A in %]
Inp A: Frequency input A
Inp B: Frequency input B
MPi
User input
LAtch
When the MPI input is activated the display is “frozen” and remains “frozen”
until the MPI input is deactivated�
Internally the frequency meter continues running�
tEAch
When the MPI input is activated the current frequency for the preset that has
just been selected will be adopted as the new preset value�