Electronic Preset Counter E89005
28
Display
Description
Submenu
Value
Loc.InP
Lock input
ProG
When the lock input is activated the programming is inhibited�
PrESET
When the lock input is activated the setting of the preset values is inhibited�
PrG.PrE
When the lock input is activated the setting of the preset values and the
programming are both inhibited�
factory settings are highlighted in grey
8.5.2 Mode
Submenues for output operations�
Display
Description
Submenu
Value
ModE
Submenu for determining the operation of the outputs
Add
Count mode ADD
Outputs active when count status ≥ preset value
Reset to zero�
Sub
Count mode SUBTRACT
Output 1 active when count status ≤ preset value 1.
Output 2 active when count status ≤ 0.
Reset to preset 2
AddAr
Count mode ADDING with automatic reset
Output 1 active when count status ≥ preset value 1.
Output 2 (timed signal) active when count status = preset value 2�
Automatic reset to zero when count status = preset value 2�
Reset to zero�
SubAr
Count mode SUBTRACTING with automatic reset
Output 1 active when count status ≤ preset value 1.
Output 2 (timed signal) active when count status = 0�
Automatic reset to preset 2 when count status = 0�
Reset to preset 2�
AddbAt
Count mode ADDING with automatic reset and Batch counter
Output 2 (timed signal) active when main counter = preset value 2�
Automatic reset to zero when main counter = preset 2�
Batch counter counts the number of automatic repetitions of preset 2�
Output 1 active when Batch counter ≥ preset 1.
Manual reset sets both counters to zero�
Electrical reset only sets the main counter to zero�