Compact speed monitor M18
DI604A
17
8.2 Parameter setting via the unit keys
Unit locking
If the LED alternately flashes yellow and green when attempting to set parameters, local
parameter setting is disabled. This locking can only be removed using an IO-Link parameter
setting software. After unlocking, parameter setting is possible via the keys on the unit.
If no key is pressed for more than 120 s the unit will automatically exit the parameter setting or
installation/set-up mode. Any unsaved parameter changes will be lost.
8.2.1 Parameter setting mode
The following parameters can be set via the unit keys:
1. Switch point SP1 (2.1...24,000 pulses/min; factory setting: 100 pulses/min)
2. Start-up delay (0…15 s, steps: 1 s; factory setting: 10 s)
(Up to 30 s can be set via IO-Link.)
3. Output function OUT1 (NO/NC; factory setting: NO)