Updating the runtime system via USB interface
61302
Requirements:
•
New runtime system has been downloaded (
).
•
Runtime system file (*.swu) has been unpacked and copied to the USB memory.
•
USB memory is connected to the unit.
•
Recovery mode is started (
→
Starting the recovery mode
(
► Click on [INSTALL FROM FILE].
>
The file browser appears.
► Select the runtime system file (*.swu).
► Click on [OPEN] to start the update process.
>
Recovery mode updates runtime system of the unit.
>
The display shows status messages
If successful:
>
Display shows status message "Success!".
► Click on [RESTART] to restart the device.
>
Updating the runtime system via web browser
61303
Requirements:
•
New runtime system has been downloaded (
).
•
The runtime system file (*.swu) has been unpacked and stored in the file system of the computer.
•
The computer is connected to the Ethernet interface ETH0 or ETH1 of the unit.
•
The unit and the computer are participants of the same IP network segment (
→
Configuring the
Ethernet interfaces
(
•
Recovery mode has been started.
► On the computer: start web browser.
► Go to the following address: http://<ipaddress>:8080 (e.g. http://192.168.178.35:8080)
>
The website of the recovery mode appears.
► Drag and drop the runtime system file to the area.
>
The update process starts automatically.
>
Recovery mode updates runtime system of the unit.
>
The display shows status messages
If successful:
>
Display shows status message "Success!".
► Click on [RESTART] to restart the device.
>
7.1.3
Restoring the data backup
61304
The user can create a data backup in the set-up mode (
→
Creating a data backup
(
)). The
recovery of the data backup (*.swu) is done via the function of the runtime update.
Requirements:
•
A valid runtime system is installed on the unit.
•
Recovery mode has been started.
► Recovering the data backup (→
Updating the runtime system
(
)).