4.8.2 Voltage output
12,0
[
V
]
11,5
10,0
0
MEW
AEP
ASP
80
100
110
-20
0
[°C]
[%]
100
120
130
11
Characteristics of the analogue output according to the standard IEC 60947-5-7
1: Output voltage
2:
Volumetric flow quantity
3: Temperature
4: Display range
5: Measuring range
6: Range between analogue start point and analogue end point
7: The unit is in the error state (FOU = OFF) or the process value transmitted in an ana-
logue way is below the display range�
8: Curve of the analogue signal at factory setting
9: Curve of the analogue signal with shifted ASP and AEP
10: The process value transmitted in an analogue way is therefore above the display
range�
11: The unit is in the error state (FOU = ON)�
ASP = analogue start point: determines at which measured value the output signal is 0 V
AEP = analogue end point: determines at which measured value the output signal is 10 V
VMR = final value of the measuring range
= 100 %
Minimum distance between ASP and AEP = 20 % of the measuring range
In the set scaling range the output signal is between 0 and 10 V�