30
9 Set-up
After power on and expiry of the power-on delay time (approx� 5 seconds) the unit
is in the normal operating mode� It carries out its measurement and evaluation
functions and generates output signals according to the set parameters�
•
During the power-on delay time the outputs are switched as programmed:
-ON with normally open function (Hno / Fno)
-OFF with normally closed function (Hnc / Fnc)�
•
If output 2 is configured as analogue output, the output signal is at 20 mA (cur-
rent output) or 10 V (voltage output)�
10 Parameter setting
Parameters can be set before installation and set-up of the unit or during opera-
tion�
If you change parameters during operation, this will influence the function�
►
Ensure that there will be no malfunctions in your plant�
During parameter setting the unit remains in the operating mode� It continues to
monitor with the existing parameter until the parameter setting has been com-
pleted�
10.1 IO-Link interface
Using an IO-Link capable parameter setting tool, the following options are avail-
able:
-Reading current process values�
-Reading, changing and saving current parameter settings and transmitting
them to other units of the same type�
The IO-Link Device Description (IODD) can be downloaded at
www�ifm�com/uk/io-link�