37
UK
10.6.7 Setting the error behaviour of the outputs
►
Select [FOU1] and set the value:
1� Switching output:
-[On] = output 1 switches ON in case of an error�
-[OFF] = output 1 switches OFF in case of an error�
-[OU1] = output 1 switches irrespective of the error as defined with the
parameters�
2� Frequency output:
-[On] = 130% of FrEP
-[OFF] = 0 Hz
-[OU1] = continues running
►
Select [FOU2] and set the value:
-[On] = output 2 switches ON in case of an error, the analogue signal
goes to the upper error value�
-[OFF] = output 2 switches OFF in case of an error, the analogue signal
goes to the lower error value�
-[OU2] = output 2 switches irrespective of the error as defined with the
parameters� The analogue signal corresponds to the measured value�
10.6.8 Configuring the empty pipe detection as diagnostic output
►
Select [OU1] or [OU2] and set [dOU]�
►
Select [P-n] and set [PnP] or [nPn]�
The empty pipe detection is only effective if it is activated at [EP�
On] → 10.6.9. When the empty pipe state is detected, the diagnostic
output is inactive�
10.6.9 Activating / deactivating empty pipe detection
►
Select [EP�On] and set the function:
-[OFF] = empty pipe detection deactivated�
-[On] = empty pipe detection activated�
10.6.10 Time-delay empty pipe detection
►
Select [dEP�E] and set the delay time from 0…30 s, at which the signal
should be provided when the pipe is empty�
►
Select [dEP�F] and set the delay time from 0…30 s, at which the signal
should be provided when the pipe is full�