11.3 Error indications
Warning message
[SC1]
Short circuit in OUT1�
LED8 for OUT1 flashes (→ 7 Operating and display elements).
[SC2]
Short circuit in OUT2�
LED7 for OUT2 flashes (→ 7 Operating and display elements).
[SC]
Short circuit in both outputs�
LED7 and LED8 flash (→ 7 Operating and display elements).
[OL]
Detection zone of volumetric flow or temperature exceeded�
Measured value between 120 % and 130 % of the final value of the
measuring range�
[UL]
Below the detection zone of volumetric flow or temperature�
Measured value between -120 % and -130 % of the final value of the
measuring range�
[Err]
• Unit faulty / malfunction�
• Measured value greater than 130 % of the final value of the meas-
uring range�
• Measured value lower than -130 % of the final value of the measur-
ing range�
[C�Loc] Setting pushbuttons locked, parameter change rejected�
Active IO-Link communication�
[S�Loc] Setting pushbuttons locked, parameter change rejected�
Unlock using parameter setting software�
[SEnS] • Sensor signal invalid�
• Measuring pipe not sufficiently filled�
• Medium with too low a conductivity�
[IOE�n] Malfunctioning� The unit is faulty and must be replaced�