10.5.2 Configure analogue value for temperature
► Select [SEL2] and set [TEMP]�
► Select [OU2] and set the function�
-[I] = temperature-proportional current signal (4…20 mA)
► Select [ASP] and set the value at which the minimum value is provided�
► Select [AEP] and set the value at which the maximum value is provided�
10.6 User settings (optional)
10.6.1 Set standard unit of measurement for volumetric flow
► Select [Uni] and set the unit of measurement: [scfm] or [scfh] or [sfs]�
The setting only has an effect on the volumetric flow value� The
counter values (consumed quantity) are automatically displayed in
the unit of measurement providing the highest accuracy�
10.6.2 Configuration of the standard display
► Select [SELd] and determine the standard measuring unit�
-[FLOW] = the current volumetric flow value in the standard unit of
measurement is displayed
-[TOTL] = the current meter reading in scf or 1000 scf
-[TEMP] = the current medium temperature in °C is displayed
► Select [diS] and set the update rate and orientation of the display�
-[d1] = update of the measured values every 50 ms
-[d2] = update of the measured values every 200 ms
-[d3] = update of the measured values every 600 ms
-[rd1], [rd2], [rd3] = display as for d1, d2, d3; rotated by 180°
-[OFF] = the display is switched off in the operating mode; when press-
ing the button the process value is displayed for 15 s�
10.6.3 Set measured value damping
► Select [dAP] and set the damping constant in seconds (τ value 63 %).