22
10.3.2 Configure limit value monitoring with OUT2
► Select [Uni] and set the unit of measurement (→ 10.6.1).
► Select [SEL2] and set [FLOW]�
► Select [OU2] and set the switching function�
-[Hno] = hysteresis function/normally open
-[Hnc] = hysteresis function/normally closed
-[Fno] = window function/normally open
-[Fnc] = window function/normally closed
► Select [SP2] and set the value at which the output switches�
► Select [rP2] and set the value at which the output resets�
10.3.3 Configure analogue value for volumetric flow
► Select [Uni] and set the unit of measurement (→ 10.6.1).
► Select [SEL2] and set [FLOW]�
► Select [OU2] and set the function�
-[I] = current signal proportional to volumetric flow (4…20 mA)
► Select [ASP] and set the value at which the minimum value is provided�
► Select [AEP] and set the value at which the maximum value is provided�
10.4 Settings for consumed quantity monitoring
10.4.1 Configure quantity monitoring via pulse output
► Select [OU1] and set [ImP]�
► Select [ImPS] and set the volumetric flow quantity at which 1 pulse is
provided (→ 10.4.3).
► Select [ImPR] and set [YES]�
> Pulse repetition is active� Output 1 provides a counting pulse each time
the value set in [ImPS] is reached�
10.4.2 Configure quantity monitoring via the preset counter
► Select [OU1] and set [ImP]�
► Select [ImPS] and set the volumetric flow quantity at which output 1
switches (→ 10.4.3).
► Select [ImPR] and set [no]�
> Pulse repetition is not active� The output switches ON if the value set in
[ImPS] is reached� It remains switched until the counter is reset�