Operating instructions 

Electronic temperature sensor

TN21xx 

TN23xx 

TN24xx 

TN26xx

80235797 / 00    02 / 2016

UK

Содержание efector 600 TN21 Series

Страница 1: ...Operating instructions Electronic temperature sensor TN21xx TN23xx TN24xx TN26xx 80235797 00 02 2016 UK ...

Страница 2: ... 9 4 4 3 Parameter setting tools 9 5 Installation 9 6 Electrical connection 10 7 Operating and display elements 11 8 Menu 12 8 1 Process value display RUN and menu structure 12 8 2 Explanation of the menu 13 9 Parameter setting 14 9 1 Parameter setting in general 15 9 1 1 Change between the menus 15 9 1 2 Change to the process value display RUN mode 15 9 1 3 Locking Unlocking 16 9 1 4 Timeout 16 9...

Страница 3: ...ns of the unit or to unwan ted effects in your application That is why installation electrical connection set up operation and maintenance of the unit must only be carried out by qualified personnel authorised by the machine operator Check the compatibility of the product materials Technical data with the media to be measured in all applications The responsibility whether the measurement devices a...

Страница 4: ...rature OUT2 2 selection options Switching signal limit values for temperature Analogue signal for temperature 4 1 Switching function OUTx changes its switching status if it is above or below the set switching limits Hysteresis or window function can be selected Hysteresis function Window function SPx rPx FHx FLx T Temperature SPx set point rPx reset point HY hysteresis Hno hysteresis NO normally o...

Страница 5: ...range This keeps the switching state of the output stable if the temperature varies slightly 4 2 Analogue function The unit converts the measured signal into a temperature proportional ana logue signal Depending on the parameter setting the output signal is at 4 20 mA ou2 I 20 4 mA ou2 Ineg 0 10 V ou2 U 10 0 V ou2 Uneg The analogue signal can be scaled that means the limits of the measuring range ...

Страница 6: ...e ASP2 analogue start point AEP2 analogue end point Within the measuring range the output signal is between 4 and 20 mA If the temperature value T is outside the measuring range the following output signal is displayed ou2 I ou2 Ineg T MAW ASP2 3 8 4 mA 20 5 20 mA T MEW AEP2 20 20 5 mA 4 3 8 mA In case of internal fault the output signal behaves according to the parameter set in FOU2 FOU2 On FOU2 ...

Страница 7: ...ange ASP2 analogue start point AEP2 analogue end point Within the measuring range the output signal is between 0 and 10 V If the temperature value T is outside the measuring range the following output signal is displayed ou2 U ou2 Uneg T MAW ASP2 0 V 10 3 10 V T MEW AEP2 10 10 3 V 0 V In case of internal fault the output signal behaves according to the parameter set in FOU2 FOU2 On FOU2 OFF ou2 U ...

Страница 8: ...ers changes according to the measured value OUT1 OUT2 OUT1 and OUT2 Colour change to Parameter r1ou r2ou r cF red G1ou G2ou G cF green 4 3 1 Parameter r1ou r2ou G1ou G2ou SP1 SP2 MAW MEW Hysteresis function Colour change if measured value is above the switch point FL1 FL2 FH1 FH2 MAW MEW Window function Colour change if measured value is within the window range MAW initial value of the measuring r...

Страница 9: ...ation is possible via a point to point connection with a USB adapter cable You will find more detailed information about IO Link at www ifm com gb io link 4 4 2 Device specific information You will find the IODDs necessary for the configuration of the IO Link unit and detailed information about process data structure diagnostic information and parameter addresses at www ifm com gb io link 4 4 3 Pa...

Страница 10: ...50178 SELV PELV Disconnect power Connect the unit as follows 4 3 2 1 BK black BN brown BU blue WH white BN WH BK BU 4 1 3 2 OUT2 L L OUT1 Colours to DIN EN 60947 5 2 Sample circuits 2 x positive switching 2 x negative switching L L 3 BU 4 BK 2 WH 1 BN L L 3 BU 4 BK 2 WH 1 BN 1 x positive switching 1 x analogue 1 x negative switching 1 x analogue L L 3 BU 4 BK 2 WH 1 BN L L 3 BU 4 BK 2 WH 1 BN Pin ...

Страница 11: ...measurement LED 3 switching status OUT2 lights if output 2 is switched 4 Alphanumeric display 4 digits Display of current temperature in red or green colour Display of the parameters and parameter values 5 Buttons up and down Select parameters Change parameter values hold button pressed Change of the display unit in the normal operating mode RUN mode Locking Unlocking press buttons simultaneously ...

Страница 12: ...n P n PnP nPn uni F C Hno Hnc Fno Fnc ou2 I Ineg U Uneg coF 10 10 C dr1 0 0 50 s dS1 0 0 50 s dr2 0 0 50 s dS2 0 0 50 s rES cFH diS coLr rEd r cF G cF GrEn r1ou G1ou r2ou G2ou cFL rd1 rd2 rd3 OFF d1 d2 d3 1 1 EF rP1 SP1 AEP2 ASP2 FH1 FL1 rP2 SP2 FH2 FL2 0 5 100 0 0 99 5 1 The parameters are only displayed when coLr r cF or G cF ...

Страница 13: ...output Hno Hysteresis function normally open Hnc Hysteresis function normally closed Fno Window function normally open Fnc Window function normally closed I current signal 4 20 mA Ineg current signal 20 4 mA U voltage signal 0 10 V Uneg voltage signal 10 0 V dS1 dS2 Switching delay on OUT1 OUT2 in seconds dr1 dr2 Switch off delay on OUT1 OUT2 in seconds FOU1 FOU2 Behavior of output OUT1 OUT2 in ca...

Страница 14: ... temperature cFL Lower limit value for colour change temperature diS Update rate and orientation of the display d1 update of the measured values every 50 ms d2 update of the measured values every 200 ms d3 update of the measured values every 600 ms rd1 rd2 rd3 display as for d1 d2 d3 rotated by 180 OFF The measured value display is deactivated in the RUN mode The LEDs remain active even if the dis...

Страница 15: ... parameter setting software at the same time tempo rary locking If S Loc is displayed the sensor is permanently locked via software This locking can only be removed with a parameter setting software 9 1 1 Change between the menus 1 Change from the RUN mode to the main menu 2 Select parameter EF 3 Change to the submenu EF 4 Select parameter CFG MEM DIS 5 Change to the submenu CFG MEM DIS 6 Return t...

Страница 16: ...yed 9 1 4 Timeout If no button is pressed for 30 s during parameter setting the unit returns to the operating mode with unchanged values 9 1 5 Configure colour change display Select coLr and define the colour of the process value display rEd GrEn r1ou G1ou r2ou G2ou r cF G cF 4 3 coLr 9 1 6 Setting of the limit values for colour change Select cFH and set the upper limit value Select cFL and set th...

Страница 17: ...ess Press or and keep pressed until is displayed Briefly press It is recommended to take down your own settings in the table before carrying out the function 12 Factory setting rES 10 Operation After power on the unit is in the RUN mode normal operating mode It carries out its measurement and evaluation functions and provides output signals accord ing to the set parameters 10 1 Reading of the set ...

Страница 18: ...UT2 flashing OL Detection zone exceeded UL Below the detection zone C Loc Setting pushbuttons locked parameter change rejected Active IO Link communication S Loc Setting pushbuttons locked parameter change rejected Unlock using parameter setting software Analogue signal in case of an error 4 2 11 Technical data Technical data and scale drawing at www ifm com ...

Страница 19: ...r setting TN2xx5 TN2xx3 SP1 60 C 140 F rP1 50 C 122 F SP2 120 C 248 F rP2 100 C 212 F ASP2 50 C 0 F AEP2 150 C 300 F uni C F ou1 Hno ou2 I dS1 0 dr1 0 dS2 0 dr2 0 FOU1 OFF FOU2 OFF P n PnP coF 0 coLr rEd diS d2 Further information at www ifm com ...