10.3 Error indication
[SC1]
Short circuit in OUT1�
[SC2]
Short circuit in OUT2�
[SC]
Short circuit in both outputs�
[OL]
Detection zone of volumetric flow or temperature exceeded:
measured value between 120 % and 130 % of VMR�
[UL]
Below the detection zone of temperature:
measured value below 14°F.
[Err]
- Unit faulty / malfunction�
- Measured value greater than 130 % of VMR�
[SEnS] Sensor indicates incorrect measurement� For more detailed diagnosis / fault
assessment:
►
Press [Set] briefly�
> The latest measured values are displayed�
[IOE]
Flow sensor faulty�
[Loc]
Setting pushbuttons locked, parameter change rejected�
VMR = final value of the measuring range
10.4 General operating conditions
►
Avoid deposits, accumulated gas and air in the pipe system�
Greater amounts of accumulated gas and air in the medium or unit generally lead
to the display [SEnS]�
For medium temperatures over 122 °F some parts of the housing can heat
up to over 140 °F.
►
In this case do not touch the unit�
►
Protect the housing against contact with flammable substances and uninten-
tional contact�
►
Do not press the pushbuttons manually; instead use an object�