5 Installation
5.1 Installation location
►
Install the unit in that section of the plant where the medium flows under pres-
sure� This avoids disturbance by air bubbles�
►
Install the unit so that the measuring pipe is always completely filled�
Arrange for inlet and outlet pipe lengths� Disturbances caused by bends,
valves, reductions, etc� are compensated for�
It applies in particular: no shut-off and control devices are allowed directly in
front of the unit�
S = disturbance; D = pipe diameter; F = flow direction
►
Install in front of or in a rising pipe�
F = flow direction