6.2.2 DC supply
► The SELV criteria (safety extra-low voltage) must be met for the DC supply�
► The DC supply cable L+ (terminal 2) must be protected externally with a 315
mA T fuse (5 x 20 mm or similar)�
The DC supply terminals are directly connected to the sensor supply terminals�
6.3 Inputs
6.3.1 Connection of the sensors (In1, 2)
DC PNP to FR-2
DC NPN to FR-2
AC/DC to FR-2
BN
BK
BU
5
6
BN
BU
5
BN
BK
BU
5
6
4 11
/
10 12
/
4 11
/
DC quadronorm to FR-2
NAMUR up to 25 V to FR-2
NAMUR 8�2 V to FR-2N
WH
BK
5
BN
BU
6
BN
BU
4 11
/
10 12
/
6 12
/
5 11
/
Connection of the sensors
The connection of mechanical switch contacts is not recommended since
they tend to bounce and produce faulty pulses�
The terminals 5/6 can be used for the sensor supply or for the reset inputs (only
F���-x)�
6.3.2 Reset inputs (reset 1 and 2)
The start-up delay can be started or a saved error can be reset via the reset inputs
(terminals 17/18)�
► The in24 V DC voltage (terminal 5) or an ex24 V DC voltage is
connected with terminal 17 or 18 via a closing contact�
Reset for output 1 = terminal 17
Reset for output 2 = terminal 18
► If an external voltage is used, the negative reference point of this voltage must
be connected to terminal 1 of the monitor�
When the contact is opened (+24 V DC no longer applied), the start-up delay or
the memory reset starts�