16
7.1.3 FWx
Function Wire Break Monitoring (only F���-xN)
Relay characteristics for wire fault or short circuit, i�e� input frequency = 0
Frequency > SPx
FWx = inactive (0)
FWx = active (1)
FOx = 1 or 4
relay energised
relay de-energised
FOx = 2 or 3
relay de-energised
relay remains de-energised
Frequency < SPx
FWx = inactive (0)
FWx = active (1)
FOx = 1 or 4
relay energised
relay de-energised
FOx = 2 or 3
relay de-energised
relay remains de-energised
Frequency in the range
FWx = inactive (0)
FWx = active (1)
FOx = 5
relay de-energised
relay remains de-energised
FOx = 6
relay energised
relay de-energised
Values
0 = inactive
1 = active
Default value
0
7.1.4 NCx
Number of Cams (on inputs 1/2)
Number of cams detected per revolution� On the basis of this value the monitor calculates
the rotational speed (measured frequency ÷ NCx = displayed speed in RPM)�
For frequency measurements NCx = 1 should remain set�
Values
1���999
Default value
1
7.1.5 DIM
Dimension (display format)
Indication in Hz or RPM (revolutions per minute)�
When a new unit is selected, the monitor converts all existing values into the new unit!
Values
0 = RPM
1 = Hz
Default value
0 = RPM