Operating instructions AX460
25
RESULT≤PRES
Display value smaller than or equal to preselection 1, e�g� underspeed
(start-up delay recommended)
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value <= preselection 1 → ON
Display value > preselection 1 + hysteresis 1 → OFF
RESULT=PRES
Display value equal to preselection 1� In combination with hysteresis 1
a frequency band (presel/- ½ hysteresis) can be defined and
monitored�
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value > preselection 1 + ½ hysteresis 1 → OFF
Display value < preselection 1 - ½ hysteresis 1 → OFF
RES≥PRES-TRAIL
Tracking preset 1:
Display value greater than or equal to preselection 2 – preselection 1
Preselection 1 is the tracking preset of preselection 2�
HYSTERESIS 1
Hysteresis to define the switch-off point for the switching condition of preselection 1
0
No switching hysteresis
…
99999
Switching hysteresis of 99999
PULSE TIME 1 (S)
Duration of the fleeting pulse (in seconds) for the switching condition of preselection 1
0�000
No fleeting pulse (static signal)
…
60�000
Pulse duration of 60 seconds
OUTPUT TARGET 1
Assignment of an output for the switching condition of preselection 1�
If several switching conditions have been assigned to one single output, this output is active as soon as
one of the switching conditions has been met�
NO
No attribution
CTRL OUT 1
Assignment of the switching condition to Ctrl� Out 1
CTRL OUT 2
Assignment of the switching condition to Ctrl� Out 2
CTRL OUT 3
Assignment of the switching condition to Ctrl� Out 3
CTRL OUT 4
Assignment of the switching condition to Ctrl� Out 4