device manual AS-i DP - Gateway
6.2 Technical data
General:
Operating voltage
AC1326: 20..30V DC (PELV)
AC1335: 26,5...31,6 DC (AS-i)
Current consumption
AC1326: < 0.4A
AC1335: < 0.2A
Operating temperature
0..+60°C
Storage temperature
-20..+70°C
Protection to DIN 40050
IP 20
Housing material
aluminium
Mounting
on DIN rail 35mm
Housing dimensions
AC1326: 107mm x 85mm x 123.6 mm
AC1335: 68mm x 85mm x 138 mm
AS-i master:
Number of AS-i masters
1 (AC1335) or 2 (AC1326)
AS-interface profile
M3 according to version 2.11
AS-interface voltage
26.5 .. 31.6V (special AS-i power supply)
AS-i current consumption
0.1 A / master (AC1326)
Microcontroller
Infinion C161 microcontroller
Supported V2.1 features
A/B slaves,
periphery fault detection,
analogue Plug+Play (7.3 profile),
ext. ID codes
Additional features
AS-i cycle counter,
communication error counter per slave,
Config error counter,
change into protected mode without AS-i reset,
easy start up
Serial RS232C port:
Baud rates
9600, 19200, 38400, 57600, 115200 bits/s
Communication parameters
8 data bits, no start bit, 1 stop bit, no parity
Connector
RJ11 Western socket, 6 poles
Profibus DP slave:
Baud rates
9.6 .. 12MBaud
Connector
SUB D 9
6-43