device manual AS-i DP - Gateway
F10
General NV mirror switching
During the change to the mirror range of the non-volatile data an error has occurred.
Possible cause:
Unacceptable interference on the 24V power supply cable during the storage operation of the
data in the flash device.
Rectification:
Repeat command.
6.1.7 General RTS error (code R01 ...
R30)
R01
Unknown RTS operating mode
Not used in Profibus DP Gateway
R02
master1: MUX field failure
R02
master2: MUX field failure
R03
master1: Protocol Error (EDET)
R04
master2: Protocol Error (EDET)
During transfer of the MUX fields from the operating system the master detected an invalid field number, the
master has detected a protocol error during transfer of the data fields.
Possible cause:
Parts of the operating system have been overwritten by the plc.
Unacceptable interference on the
24V cable.
R06
General RTS program failure
The operating system has found an invalid state in the process of the internal program processing.
Possible cause:
Operating system software error.
R07
Projecting mode not active
The attempt was made to execute an AS-i command which is only permitted in the “Projection Mode”.
Rectification:
Switching the master into the “Projection Mode” operating mode in the "master Setup"-> "Operating
Mode" menu.
R08
No PLC program loaded
Not used in AS-i DP Gateway
R09
RS-232 frame error (Baudrate)
The hardware of the integrated serial interface chip has found a transfer error in the RS-232 data flow.
Possible cause:
The baud rate setting on the connected PC shows another setting than that on the device.
Rectification:
Adapting the baud rate in the "System Setup"->"Baud Rate" menu. (AC1326)
R10
RS-232 buffer overflow
A buffer overflow was found in the serial receive buffer of the RS-232 interface.
Possible cause:
DOS via RS-232, defective RS-232 cable. (AC1326)
R11
RS-232 parity check
The parity check of the serial data flow of the RS-232 interface was unsuccessful. (AC1326)